{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-6HL32-0DL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-6HL32-0DL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-6HL32-0DL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HL32-0DL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-6HL32-0DL0, molded case circuit breaker, 3-pole, 100 A, 242 kA at 240 V, line protection, ETU320 release, undervoltage release.","salesMarkdown":"The interrupting ratings are the headline: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 5 kA at 690 V. The thermal derating curve is flat from 40 °C to 50 °C at full 100 A, then steps down: 96.25 A at 55 °C, 92.5 A at 60 °C, 88.75 A at 65 °C, and 85 A at 70 °C. The maximum power loss is 12.5 W, which is modest for a 100 A frame; helps keep internal cabinet temperature rise manageable. ## Auxiliary and undervoltage release fit The UVR is factory-fitted as part of the basic switch assembly (3VA2110-6HL32-0AA0) and the auxiliary trip module is order code 3VA9608-0BB25. If you're replacing an existing MCCB in a panel that uses UVR for emergency-stop or undervoltage protection, this variant drops in without rewiring the shunt trip circuit. That's a standard 3VA2 frame footprint — same width as the 3VA1 series, so it fits the same DIN-rail or screw-mount baseplates.","metaTitle":"Siemens 3VA2110-6HL32-0DL0 SENTRON MCCB, 100 A, 3-Pole, 242","metaDescription":"Siemens SENTRON 3VA2110-6HL32-0DL0 molded case circuit breaker, 100 A rated, 3-pole, 242 kA breaking at 240 V. Current lifecycle. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"12.5 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2110-6HL32-0AA0","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB25","Design of the overcurrent release":"ETU320","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"150 A","Adjustable response value current / lr min.":"40 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"4","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=288339&mlfb=3VA2110-6HL32-0DL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HL32-0DL0/alternatives.json"},"ai":{"faq":[{"question":"What are the key interrupting ratings for 3VA2110-6HL32-0DL0?","answer":"It breaks 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 5 kA at 690 V. That covers high-fault industrial panels up to 500 V."},{"question":"What auxiliary contacts come with this MCCB?","answer":"It includes 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch (HQ type), plus a factory-fitted undervoltage release."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-6HL32-0DL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-6HL32-0DL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}