{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-6HL32-0HH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-6HL32-0HH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-6HL32-0HH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HL32-0HH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-6HL32-0HH0, molded case circuit breaker, 3-pole, 100 A, ETU320 electronic trip unit, line protection, shunt trip, 242 kA at 240 V.","salesMarkdown":"## 3VA2110-6HL32-0HH0 — SENTRON MCCB, 100 A Frame, 242 kA Interrupting at 240 V The Siemens 3VA2110-6HL32-0HH0 is a 3-pole SENTRON molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current Iu of 100 A at 40 °C through 50 °C, derating to 85 A at 70 °C. The interrupting capacity hits 242 kA at 240 V, 187 kA at 415/440 V, 121 kA at 500 V, and 5 kA at 690 V — that 242 kA figure at 240 V means it can safely clear a fault on a high-capacity transformer secondary or a large capacitor bank without the arc re-striking. ## Trip Unit and Auxiliaries Fitted with the ETU320 electronic overcurrent release — this is the basic electronic trip offering in the 3VA line, providing adjustable thermal-magnetic curves via DIP switches on the front face, not the full LCD of the ETU600 series. The shunt trip (STL) auxiliary release is built in (design of the auxiliary release: shunt trip), so a remote trip coil is already wired to the secondary terminals; no external undervoltage release is present. That 86 mm depth is the critical dimension when recessing into a panel backplate — verify the enclosure depth allows for the rear-mounted terminals and the shunt trip wiring tray. Mounts directly to the DIN rail or the 3VA mounting plate; the 105 mm width occupies three 35 mm module spaces. Maximum power dissipation is 10 W, so no forced cooling required in a standard IP54 enclosure, but keep it away from heat sources like contactor coils or power supplies.","metaTitle":"Siemens 3VA2110-6HL32-0HH0 SENTRON MCCB, 100 A, 242 kA at 24","metaDescription":"Siemens 3VA2110-6HL32-0HH0 SENTRON molded case circuit breaker, 100 A rated, 242 kA breaking capacity at 240 V. ETU320 release, shunt trip. Current production. Sourced to order aga","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"10 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2110-6HL32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL30","Design of the overcurrent release":"ETU320","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"150 A","Adjustable response value current / lr min.":"40 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=244313&mlfb=3VA2110-6HL32-0HH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HL32-0HH0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2110-6HL32-0HH0 at 240 V?","answer":"242 kA at 240 V. That drops to 187 kA at 415 V and 440 V, 121 kA at 500 V, and 5 kA at 690 V."},{"question":"What trip unit does 3VA2110-6HL32-0HH0 use?","answer":"The ETU320 electronic overcurrent release. It is the entry-level electronic trip in the 3VA family, with adjustable settings via DIP switches."},{"question":"Does 3VA2110-6HL32-0HH0 include a shunt trip?","answer":"Yes, the design of the auxiliary release is a shunt trip (STL). No undervoltage release is fitted."},{"question":"What are the physical dimensions of 3VA2110-6HL32-0HH0?","answer":"105 mm wide, 181 mm high, 86 mm deep. The 86 mm depth is the key fit dimension for panel backplate clearance."},{"question":"How do I get current pricing and availability for 3VA2110-6HL32-0HH0?","answer":"Submit an RFQ through this listing. The part is sourced to order through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"Will 3VA2110-6HL32-0HH0 drop into a panel specified for 3VA1110-5EE32-0JA0?","answer":"The 3VA2110 frame is physically larger (105 mm wide vs the 3VA1110's 55 mm) and uses a different mounting plate. It will not fit the same DIN-rail footprint or panel cutout without rewiring and a new backplate layout."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-6HL32-0HH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-6HL32-0HH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}