{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-6HL32-0KH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-6HL32-0KH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-6HL32-0KH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HL32-0KH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-6HL32-0KH0, molded case circuit breaker, 3-pole, 100 A continuous rating, 242 kA breaking capacity at 240 V AC, line protection design.","salesMarkdown":"The interrupting capacity tells you where this breaker can be applied: 242 kA at 240 V AC, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3.7 kA at 690 V. This is a line-protection device (not a motor-protection or generator-protection variant), so it's sized for cable and busbar protection in a main or feeder breaker role. The 3VA2 frame is the higher-interrupting series within the SENTRON family, suited for installations where SCCR requirements are demanding. That means you get remote status indication and remote tripping capability out of the box — no separate aux kit to order. The shunt trip allows a PLC or safety relay to open the breaker on demand, which is useful for emergency-stop circuits or interlocking schemes. If UVR or GF protection is needed, that's a different order code within the 3VA2 family. The trip indicator and voltage trigger features are present, so local visual trip indication is standard. The 86 mm depth means it protrudes less than older SENTRON frames, which can help with shallow enclosure fit. Maximum power loss is 10 W, which is moderate for a 100 A MCCB. In a sealed enclosure with multiple breakers, that heat adds up — factor it into your thermal budget rather than assuming zero dissipation. The 100 A rating is continuous at any temperature within the operating range, so no summer derating worry.","metaTitle":"Siemens 3VA2110-6HL32-0KH0 SENTRON MCCB, 100 A, 3-Pole, 242","metaDescription":"Siemens SENTRON 3VA2110-6HL32-0KH0 molded case circuit breaker, 100 A continuous, 3-pole, 242 kA breaking at 240 V. Active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3.7 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21106HL320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL33","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=53671&mlfb=3VA2110-6HL32-0KH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HL32-0KH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2110-6HL32-0KH0 and how is it quoted?","answer":"This MCCB is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is the closest functional second-source to 3VA2110-6HL32-0KH0?","answer":"The 3VA2116-5HL32-0AK0 is a higher-current sibling in the same 3VA2 frame family, but it has a different continuous rating and aux configuration. For a direct 100 A drop-in with the same aux layout, stick with this order code — the frame footprint is identical, but the trip unit and rating plug differ."},{"question":"Will 3VA2110-6HL32-0KH0 drop into a panel specified for 3VA2116-5HL32-0AK0?","answer":"Yes, the physical footprint is the same — same 105 mm width, same mounting pattern. The difference is the continuous current rating (100 A vs higher) and the aux switch configuration. No rewiring needed for the breaker position itself, but verify the trip unit settings match your protection coordination study."},{"question":"What compliance documentation does Siemens provide for this MCCB?","answer":"As a current-production SENTRON MCCB, it carries CE marking for the European market and is designed to meet IEC 60947-2. UL and CSA listings are typical for the 3VA2 series, but confirm the specific listing for this order code against your jurisdiction's requirements. RoHS and REACH declarations are available from Siemens."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-6HL32-0KH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-6HL32-0KH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}