{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-6HL36-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-6HL36-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-6HL36-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HL36-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2, Molded case circuit breaker, 3VA2110-6HL36-0AA0, 100 A, 3-pole, ETU320 electronic trip unit, 242 kA interrupting at 240 V AC.","salesMarkdown":"## What this MCCB delivers It carries 100 A continuous current (Iu) across the full ambient range from 40 °C to 70 °C with no derating — that is a flat thermal curve, so the same 100 A holds even in a hot enclosure. Interrupting capacity is the headline here: 242 kA at 240 V AC, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3.7 kA at 690 V. At 690 V the rating drops to 3.7 kA, which is still adequate for most motor-control center applications at that voltage. Physical footprint: 105 mm wide, 181 mm tall, 86 mm deep. The ETU320 release is field-configurable for overload pickup (Ir) and short-time pickup (Isd).","metaTitle":"Siemens 3VA2110-6HL36-0AA0 SENTRON MCCB, 100 A, 3-Pole, ETU3","metaDescription":"Siemens 3VA2110-6HL36-0AA0 SENTRON molded case circuit breaker, 100 A continuous, 3-pole, ETU320 release, 242 kA at 240 V. Current lifecycle. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3.7 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","rated insulation voltage Ui":"800 V","Courant permanent assigné Iu":"100 A","Ground-Fault Monitoring Version":"Without","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","reference code / acc. to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"150 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Max. rated operational current of the frame size":"160 A","Mechanical Service Life (Switching Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (6-120 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$257.81","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=198402&mlfb=3VA2110-6HL36-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HL36-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What trip unit does 3VA2110-6HL36-0AA0 use?","answer":"It uses the ETU320 electronic trip unit, which provides adjustable overload (Ir), short-time (Isd), and instantaneous (Ii) protection settings. Ground-fault monitoring is not included on this variant."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-6HL36-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-6HL36-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}