{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-6HN32-0AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-6HN32-0AB0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-6HN32-0AB0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HN32-0AB0","rawCanonicalId":null},"summary":{"shortDescription":"SENTRON 3VA2110-6HN32-0AB0, molded case circuit breaker, 3-pole, 100 A rated continuous current, breaking capacity 242 kA at 240 V, ETU350 overcurrent release, IP40 front, current production.","salesMarkdown":"## Line protection MCCB with ETU350 — 100 A continuous, 242 kA breaking at 240 V The SENTRON 3VA2110-6HN32-0AB0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current (Iu) at 40 °C, with a rated insulation voltage (Ui) of 800 V. Its ETU350 overcurrent release provides adjustable protection for line-feeder and main-switch applications. The breaking capacity hits 242 kA at 240 V, 187 kA at 415 V, and 121 kA at 500 V — numbers that matter for high-fault panels where SCCR coordination is critical. At 690 V the capacity drops to 5 kA, so this is not a 690 V main breaker; it lives in the 240–500 V range. The 100 A rating holds flat from 40 °C to 50 °C, then derates linearly to 85 A at 70 °C. In a warm enclosure — say 55 °C ambient — you get 96.25 A, so a 100 A load at that temperature needs a larger frame or forced ventilation. The IP40 front means no gasket seal; keep it in a locked cabinet or behind a panel door.","metaTitle":"SENTRON 3VA2110-6HN32-0AB0 MCCB, 100 A, 242 kA at 240 V","metaDescription":"SENTRON 3VA2110-6HN32-0AB0 molded case circuit breaker, 100 A rated continuous current, 242 kA breaking capacity at 240 V, 3-pole, ETU350 release, IP40 front. Current production. O","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"10 W","Auxiliary contact version":"2 auxiliary switches HP","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2110-6HN32-0AA0","Design of the auxiliary release":"Without auxiliary release","Ground fault monitoring version":"Without","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.4 s","Adjustable response value time / tsd min.":"0.02 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"1 200 A","Adjustable response value current / lr min.":"40 A","Adjustable response value current / Isd max.":"1 000 A","Adjustable response value current / Isd min.":"150 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA11","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=410055&mlfb=3VA2110-6HN32-0AB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HN32-0AB0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2110-6HN32-0AB0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is 3VA2110-6HN32-0AB0's depth?","answer":"The depth is 86 mm, with a width of 105 mm and height of 181 mm."},{"question":"What breaking capacity does this MCCB offer at 240 V?","answer":"At 240 V the breaking capacity is 242 kA. At 415 V it is 187 kA, at 500 V it is 121 kA, and at 690 V it drops to 5 kA."},{"question":"Will 3VA2110-6HN32-0AB0 drop into a panel specified for 3VA1110-5EE32-0DC0?","answer":"Both are 3-pole SENTRON MCCBs with similar dimensions, but the 3VA2110-6HN32-0AB0 uses an ETU350 release and carries different breaking capacities. Verify the panel's SCCR requirements and the existing cutout dimensions before substitution."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-6HN32-0AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-6HN32-0AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}