{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-6HN32-0AJ0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-6HN32-0AJ0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-6HN32-0AJ0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HN32-0AJ0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-6HN32-0AJ0, molded case circuit breaker, 3-pole, 100 A continuous, line protection, breaking capacity 242 kA at 240 V.","salesMarkdown":"## MCCB for line protection — 100 A, 3-pole, 242 kA interrupting The Siemens SENTRON 3VA2110-6HN32-0AJ0 is a 3-pole molded case circuit breaker rated for 100 A continuous current, designed specifically for line protection duty. Its interrupting capacity reaches 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3.7 kA at 690 V — meaning it can safely clear faults across a wide voltage range without cascading upstream. The 800 V rated insulation voltage gives headroom for 480 V and 600 V class systems. At 105 mm wide, 181 mm tall, and 86 mm deep, this MCCB fits standard SENTRON panel footprints and mounts on a DIN rail or direct panel. The 100 A rating holds across the full ambient range from -25 °C to 70 °C with no derating — so it delivers its full continuous current even in a warm enclosure.","metaTitle":"Siemens 3VA2110-6HN32-0AJ0 SENTRON MCCB, 100 A, 3-Pole, 242","metaDescription":"Siemens SENTRON 3VA2110-6HN32-0AJ0 molded case circuit breaker, 100 A continuous, 3-pole, line protection. Breaking capacity 242 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"1 200 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3.7 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21106HN320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HP","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB11","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=283556&mlfb=3VA2110-6HN32-0AJ0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HN32-0AJ0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2110-6HN32-0AJ0 and get a price?","answer":"We source this part to order against an RFQ through independent distribution. Submit a request for quote to confirm current availability and pricing."},{"question":"What is the breaking capacity of 3VA2110-6HN32-0AJ0 at different voltages?","answer":"242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3.7 kA at 690 V."},{"question":"Will 3VA2110-6HN32-0AJ0 drop into a panel specified for 3VA2116-5HL32-0AK0?","answer":"The 3VA2110-6HN32-0AJ0 is a 100 A, 3-pole MCCB in the same SENTRON 3VA platform, so it shares the same mounting footprint and DIN-rail compatibility. Verify the auxiliary switch configuration and trip characteristics against your panel design — the 3VA2110 carries 2 auxiliary switches plus 1 trip alarm switch."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-6HN32-0AJ0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-6HN32-0AJ0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}