{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-6HN32-0DC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-6HN32-0DC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-6HN32-0DC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HN32-0DC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-6HN32-0DC0, molded case circuit breaker, 3-pole, 100 A continuous, 242 kA interrupting at 240 V, with undervoltage release and 2 auxiliary switches HQ.","salesMarkdown":"## Siemens 3VA2110-6HN32-0DC0 — SENTRON MCCB for Line Protection It's a 3-pole unit built on a 1200 A frame, meaning the physical housing and contacts are sized for much higher current, giving this 100 A rating generous thermal margin in the enclosure. Interrupting capacity is 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3.7 kA at 690 V. ## Built-in Undervoltage Release and Auxiliary Switches The two auxiliary switches give status feedback (open/closed) to a PLC or indicator lamp without needing an add-on block. The design is line protection (not motor protection), so it's intended for feeder or distribution duty rather than direct motor overload. No ground-fault monitoring module is included. Verify the mounting hole pattern against your existing backpanel layout.","metaTitle":"Siemens 3VA2110-6HN32-0DC0 SENTRON MCCB, 100 A, 3-Pole, 242","metaDescription":"Siemens SENTRON 3VA2110-6HN32-0DC0 molded case circuit breaker. 100 A continuous, 3-pole, 242 kA interrupting at 240 V. Undervoltage release, 2 aux switches. Current production. So","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"1 200 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3.7 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"12.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21106HN320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=355488&mlfb=3VA2110-6HN32-0DC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HN32-0DC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2110-6HN32-0DC0 and get a price?","answer":"This breaker is sourced to order against an RFQ through independent distribution. Submit a request for quote (RFQ) — availability and current pricing are confirmed at quote time."},{"question":"What is the interrupting capacity of 3VA2110-6HN32-0DC0 at 240 V?","answer":"242 kA at 240 V, dropping to 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3.7 kA at 690 V."},{"question":"Does 3VA2110-6HN32-0DC0 include an undervoltage release?","answer":"Yes, it ships with a factory-installed undervoltage release (UVR) and two HQ auxiliary switches."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-6HN32-0DC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-6HN32-0DC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}