{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-6HN32-0HC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-6HN32-0HC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-6HN32-0HC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HN32-0HC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-6HN32-0HC0, molded case circuit breaker, 3-pole, 100 A rated current, 242 kA breaking capacity at 240 V, line protection design.","salesMarkdown":"The Siemens SENTRON 3VA2110-6HN32-0HC0 is a 3-pole molded case circuit breaker rated for 100 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. The design is line protection, meaning it's optimized for upstream fault clearing rather than motor or generator protection. ## Sizing and selectivity for the panel builder At 100 A flat-rated through 70 °C, this breaker eliminates the guesswork on panel internal temperature rise — you don't have to knock down the trip setting for a warm enclosure. The 3VA series uses a common frame size across the 100 A to 1600 A range, so the mounting footprint and bus connections are consistent within the family. That makes coordination studies simpler when you're cascading downstream breakers. The supplied basic switch is 3VA21106HN320AA0. Power loss is rated at 10 W maximum.","metaTitle":"Siemens 3VA2110-6HN32-0HC0 SENTRON MCCB, 100 A, 3-Pole, 242","metaDescription":"Siemens SENTRON 3VA2110-6HN32-0HC0 molded case circuit breaker, 100 A rated, 3-pole, 242 kA breaking at 240 V. Line protection with shunt trip. Active production. Available to orde","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"1 200 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3.7 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21106HN320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL30","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=174992&mlfb=3VA2110-6HN32-0HC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HN32-0HC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2110-6HN32-0HC0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is the breaking capacity of 3VA2110-6HN32-0HC0 at 240 V?","answer":"The breaking capacity is 242 kA at 240 V. At 415 V and 440 V it is 187 kA, at 500 V it is 121 kA, and at 690 V it is 3.7 kA."},{"question":"What auxiliary components come with this breaker?","answer":"It includes a shunt trip (STL) release and two HQ auxiliary switches pre-installed."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-6HN32-0HC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-6HN32-0HC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}