{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-6HN32-0HH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-6HN32-0HH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-6HN32-0HH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HN32-0HH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-6HN32-0HH0, molded case circuit breaker, 3-pole, 100 A rated continuous current, 242 kA breaking capacity at 240 V, line protection with ETU350 electronic trip unit.","salesMarkdown":"The Siemens SENTRON 3VA2110-6HN32-0HH0 is a 3-pole molded case circuit breaker rated for 100 A continuous current (Iu) at up to 50 °C ambient, with an ETU350 electronic trip unit for line protection. Its interrupting capacity hits 242 kA at 240 V and 187 kA at 415 V, meaning it can clear high-fault currents on a 400 V distribution bus without upstream coordination issues. At 240 V the breaker clears 242 kA; at 415 V and 440 V it holds 187 kA, dropping to 121 kA at 500 V and 5 kA at 690 V. The 100 A rating holds flat from 40 °C to 50 °C; above 50 °C it derates to 96.25 A at 55 °C, 92.5 A at 60 °C, 88.75 A at 65 °C, and 85 A at 70 °C. If your panel ambient runs 60 °C, size the load at 92.5 A max. ## Auxiliary contacts and trip options","metaTitle":"Siemens 3VA2110-6HN32-0HH0 SENTRON MCCB, 100 A, 3-pole, 242","metaDescription":"Siemens SENTRON 3VA2110-6HN32-0HH0 molded case circuit breaker, 100 A, 3-pole, 242 kA at 240 V. Line protection with ETU350 release. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"10 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2110-6HN32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL30","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.4 s","Adjustable response value time / tsd min.":"0.02 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"1 200 A","Adjustable response value current / lr min.":"40 A","Adjustable response value current / Isd max.":"1 000 A","Adjustable response value current / Isd min.":"150 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=153084&mlfb=3VA2110-6HN32-0HH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HN32-0HH0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2110-6HN32-0HH0 at 415 V?","answer":"It clears 187 kA at 415 V, which is the same rating as at 440 V."},{"question":"Where can I buy 3VA2110-6HN32-0HH0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-6HN32-0HH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-6HN32-0HH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}