{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-6HN36-0AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-6HN36-0AB0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-6HN36-0AB0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HN36-0AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-6HN36-0AB0, molded case circuit breaker, 3-pole, 100 A, 242 kA at 240 V, ETU350 trip unit, IP40 front.","salesMarkdown":"The Siemens 3VA2110-6HN36-0AB0 is a SENTRON molded case circuit breaker (MCCB) rated for 100 A continuous current with an interrupting capacity of 242 kA at 240 V — that's the headline number for this frame size, meaning it can safely clear a fault up to 242,000 amps without welding its contacts or rupturing the case. At 415 V it still holds 187 kA, and at 690 V it's rated 5 kA, so the interrupting curve drops fast once you push past 500 V. The overcurrent release is an ETU350 electronic trip unit — that's the middle-tier electronic trip in the 3VA line, giving you adjustable long-time, short-time, and instantaneous pickup settings plus ground-fault alarm capability (though this specific variant ships without ground-fault monitoring). ## Panel fit and thermal derating Footprint is 105 mm wide, 181 mm tall, 86 mm deep — standard 3-pole MCCB envelope for a 100 A frame. Thermal derating is published: it holds full 100 A up to 50 °C ambient, then drops to 96.25 A at 55 °C, 92.5 A at 60 °C, 88.75 A at 65 °C, and 85 A at 70 °C. That's a clean linear derate curve — useful if you're packing this into a hot panel near a drive or transformer. ## What the interrupting ratings mean for your fault study At 415/440 V it still delivers 187 kA, and at 500 V it's 121 kA — still very high for a 100 A frame. Only at 690 V does it drop to 5 kA, which is typical for this voltage class.","metaTitle":"Siemens 3VA2110-6HN36-0AB0 SENTRON MCCB, 100 A, 242 kA at 24","metaDescription":"Siemens 3VA2110-6HN36-0AB0 SENTRON molded case circuit breaker, 100 A rated continuous current, 242 kA interrupting at 240 V. Active production. Quoted to order. Request RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"10 W","Auxiliary contact version":"2 auxiliary switches HP","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2110-6HN36-0AA0","Design of the auxiliary release":"Without auxiliary release","Ground fault monitoring version":"Without","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.4 s","Adjustable response value time / tsd min.":"0.02 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"1 200 A","Adjustable response value current / lr min.":"40 A","Adjustable response value current / Isd max.":"1 000 A","Adjustable response value current / Isd min.":"150 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA11","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (6-120 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=243327&mlfb=3VA2110-6HN36-0AB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HN36-0AB0/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does Siemens provide for this MCCB?","answer":"As a current-production SENTRON component, it carries CE marking for the European market and is UL/CSA recognized for North American installations. RoHS and REACH declarations are available through Siemens' standard documentation portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-6HN36-0AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-6HN36-0AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}