{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-6HN36-0AH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-6HN36-0AH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-6HN36-0AH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HN36-0AH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-6HN36-0AH0, molded case circuit breaker, 3-pole, 100 A, ETU350 electronic trip unit, line protection, 242 kA at 240 V.","salesMarkdown":"This 3-pole unit delivers 242 kA interrupting capacity at 240 V and 187 kA at 415 V, with a minimum of 5 kA at 690 V — covering most industrial distribution panels and motor control center infeeds. The 100 A rating holds flat from 40 °C through 50 °C, then derates linearly to 85 A at 70 °C (–). For a panel that runs warm — say a packed MCC bucket at 55 °C — the usable current drops to 96.25 A, so the breaker should be upsized if the load is continuous at the full 100 A. This makes the breaker suitable for selective coordination studies — you can set the short-time delay to ride through downstream faults without nuisance tripping the main. ## Physical fit and integration ## Comparison note against a sibling The closest functional sibling is the 3VA2110-7HK42-0AA0, which shares the same 100 A frame and 3-pole count but carries a different trip unit configuration. The 3VA2110-6HN36-0AH0 includes the HQ auxiliary contact block (2 aux + 1 trip alarm) as standard.","metaTitle":"Siemens 3VA2110-6HN36-0AH0 SENTRON MCCB, 100 A, 242 kA at 24","metaDescription":"Siemens 3VA2110-6HN36-0AH0 SENTRON molded case circuit breaker, 100 A rated, 3-pole, ETU350 trip unit, 242 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"10 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2110-6HN36-0AA0","Design of the auxiliary release":"Without auxiliary release","Ground fault monitoring version":"Without","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.4 s","Adjustable response value time / tsd min.":"0.02 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"1 200 A","Adjustable response value current / lr min.":"40 A","Adjustable response value current / Isd max.":"1 000 A","Adjustable response value current / Isd min.":"150 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (6-120 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=158511&mlfb=3VA2110-6HN36-0AH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HN36-0AH0/alternatives.json"},"ai":{"faq":[{"question":"Will the 3VA2110-6HN36-0AH0 replace the 3VA2110-7HK42-0AA0 without rewiring?","answer":"The physical footprint and bus-bar spacing are identical, so the power connections fit. However, verify the auxiliary contact configuration (2 aux + 1 trip alarm on this unit) and the trip-unit settings (ETU350) against the sibling's spec before substituting — control wiring may differ."},{"question":"What compliance documentation is available for this breaker?","answer":"As a Siemens SENTRON MCCB, it carries the relevant IEC/UL certifications for molded case circuit breakers. Specific RoHS, REACH, UL, and IEC declarations are available from Siemens upon request through the supply chain."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-6HN36-0AH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-6HN36-0AH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}