{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-6HN36-0CH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-6HN36-0CH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-6HN36-0CH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HN36-0CH0","rawCanonicalId":null},"summary":{"shortDescription":"SENTRON 3VA2110-6HN36-0CH0 molded case circuit breaker, 100 A continuous, 3-pole, 242 kA SCCR at 240 V, undervoltage release, 2 auxiliary switches + 1 trip alarm.","salesMarkdown":"The SENTRON 3VA2110-6HN36-0CH0 is a 3-pole molded case circuit breaker rated for 100 A continuous current across the full ambient range of 40 °C to 70 °C — no derating needed up to that ceiling. Its interrupting capacity hits 242 kA at 240 V, dropping to 187 kA at 415/440 V, 121 kA at 500 V, and 3.7 kA at 690 V. That SCCR headroom covers most industrial fault scenarios without cascading upstream. Line protection design, so it's the primary overcurrent device on a feeder or branch — not a motor-protector or ground-fault variant. Undervoltage release (UVR) built in, with two auxiliary switches plus a separate trip alarm switch (HQ type). ## Sizing and coordination The 242 kA SCCR at 240 V lets you coordinate downstream breakers without worrying about series rating limits; at 690 V the 3.7 kA figure is still enough for most 690 V distribution. Panel depth needed: 86 mm, width 105 mm, height 181 mm.","metaTitle":"SENTRON 3VA2110-6HN36-0CH0 MCCB, 100 A, 3-Pole, 242 kA at 24","metaDescription":"SENTRON 3VA2110-6HN36-0CH0 molded case circuit breaker, 100 A continuous, 3-pole, SCCR 242 kA at 240 V. Current lifecycle stage. Available to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"1 200 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3.7 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"12.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21106HN360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB24","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=299352&mlfb=3VA2110-6HN36-0CH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HN36-0CH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2110-6HN36-0CH0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing."},{"question":"What is the SCCR of 3VA2110-6HN36-0CH0 at 240 V?","answer":"242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3.7 kA at 690 V."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-6HN36-0CH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-6HN36-0CH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}