{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-6HN36-0CL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-6HN36-0CL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-6HN36-0CL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HN36-0CL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-6HN36-0CL0, molded case circuit breaker, 3-pole, 100 A continuous, 242 kA at 240 V, line protection design with undervoltage release and auxiliary switches.","salesMarkdown":"That 100 A holds steady at 45, 50, 55, 60, 65, and 70 °C, so it's a solid choice for a warm enclosure or a panel sitting next to a heat source. Breaking capacity hits 242 kA at 240 V, drops to 187 kA at 415 V and 440 V, then 121 kA at 500 V, and 3.7 kA at 690 V. An undervoltage release (UVR) is fitted, so the breaker will trip if control voltage drops below the release threshold, which is useful for emergency-stop chains or undervoltage protection schemes. The 86 mm depth leaves room for rear-connection busbars or a cable-entry gland plate without pushing the enclosure door out. ## Environmental and operating limits No ground-fault monitoring version is fitted; this is a plain line-protection MCCB.","metaTitle":"Siemens 3VA2110-6HN36-0CL0 SENTRON MCCB, 100A, 3-Pole, 242kA","metaDescription":"Siemens SENTRON 3VA2110-6HN36-0CL0 molded case circuit breaker, 100A continuous, 3-pole, 242kA at 240V. Active production. Sourced to order. Get a quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"1 200 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3.7 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"12.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21106HN360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB24","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=29230&mlfb=3VA2110-6HN36-0CL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HN36-0CL0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2110-6HN36-0CL0 and how do I get a price?","answer":"This part is sourced to order against an RFQ through our independent distribution channel. Submit a quote request; availability and current pricing are confirmed at quote time."},{"question":"What are the key ratings for 3VA2110-6HN36-0CL0?","answer":"Continuous current rating is 100 A (no derating up to 70 °C). Breaking capacity is 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3.7 kA at 690 V. It is a 3-pole molded case circuit breaker with undervoltage release and four auxiliary switch outputs."},{"question":"What is the depth of 3VA2110-6HN36-0CL0?","answer":"The depth is 86 mm (3.39 inches). Overall dimensions are 181 mm high by 105 mm wide by 86 mm deep."},{"question":"Does 3VA2110-6HN36-0CL0 drop into a panel designed for 3VA1110-5EF32-0AM0?","answer":"Both are 3-pole SENTRON MCCBs with the same 105 mm width, so the DIN-rail or mounting-plate footprint is the same. However, the auxiliary switch configuration and release options differ — verify the wiring of the undervoltage release and alarm contacts against your panel schematic before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-6HN36-0CL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-6HN36-0CL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}