{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-6HN36-0DL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-6HN36-0DL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-6HN36-0DL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HN36-0DL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-6HN36-0DL0, molded case circuit breaker, 3-pole, 100 A continuous at 40 °C, 1200 A frame, 242 kA interrupting at 240 VAC, line protection with undervoltage release.","salesMarkdown":"## MCCB for high-fault panel positions The Siemens 3VA2110-6HN36-0DL0 is a SENTRON molded case circuit breaker rated for 100 A continuous current across the full 40 °C to 70 °C ambient range — no derating needed up to the enclosure's thermal limit. Built on a 1200 A frame, it delivers 242 kA interrupting capacity at 240 VAC and 187 kA at 415 VAC, so it handles utility-transformer-level fault currents without cascading upstream. The 3-pole design is configured for line protection and includes an undervoltage release (UVR) as the auxiliary release, plus a complement of 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch (HQ type) for status feedback to a PLC or remote I/O. ## What the interrupting ratings mean for panel coordination The 242 kA at 240 V and 187 kA at 415 V are the maximum fault currents this MCCB can safely interrupt — values typically found at the main lug of a large distribution panel or downstream of a transformer. At 690 V the rating drops to 3.7 kA, which still covers most motor-circuit fault levels but confirms this breaker is sized for 480 V and below in high-available-current installations. The 1200 A frame means the internal mechanism and contacts are physically larger than a 100 A breaker needs, giving mechanical headroom for the high interrupting duty. ## Integration into a panel — dimensions and wiring The breaker measures 105 mm wide, 181 mm tall, and 86 mm deep — a standard 3-pole MCCB footprint that fits most DIN-rail or panel-mount enclosures without special adapters. The auxiliary switch block (2 aux + 1 trip alarm + 1 electrical alarm HQ) is factory-integrated, so no field assembly of add-on modules is needed. The undervoltage release is also installed; verify that the UVR coil voltage matches the control circuit before energizing. The basic switch assembly carries order code 3VA21106HN360AA0 for spare-part traceability.","metaTitle":"Siemens 3VA2110-6HN36-0DL0 SENTRON MCCB, 100 A, 1200 A Frame","metaDescription":"Siemens 3VA2110-6HN36-0DL0 SENTRON molded case circuit breaker, 100 A continuous, 1200 A frame, 242 kA IC at 240 VAC. 3-pole, line protection, UVR included. Current lifecycle stage","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"1 200 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3.7 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"12.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21106HN360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=231780&mlfb=3VA2110-6HN36-0DL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HN36-0DL0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2110-6HN36-0DL0 and what is the lead time?","answer":"This MCCB is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm lead-time and price."},{"question":"What is the interrupting capacity of 3VA2110-6HN36-0DL0 at 240 V?","answer":"242 kA at 240 VAC, which is the highest rating on this breaker and suits main-service positions with high available fault current."},{"question":"Does 3VA2110-6HN36-0DL0 include auxiliary switches?","answer":"Yes, it comes with 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch (HQ type) factory-installed."},{"question":"What is the continuous current rating of 3VA2110-6HN36-0DL0?","answer":"100 A continuous at 40 °C, and it holds that rating all the way up to 70 °C without derating."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-6HN36-0DL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-6HN36-0DL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}