{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-6HN36-0HH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-6HN36-0HH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-6HN36-0HH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HN36-0HH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 series, molded case circuit breaker (MCCB), 3VA2110-6HN36-0HH0, 100 A rated continuous current, 242 kA interrupting capacity at 240 V AC, 3-pole, line protection, with shunt trip (STL) and 2 auxiliary + 1 alarm switch.","salesMarkdown":"The Siemens SENTRON 3VA2110-6HN36-0HH0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current at 40 °C, with a line protection release (ETU350) and a shunt trip (STL) auxiliary release. Its interrupting capacity reaches 242 kA at 240 V AC, stepping down to 187 kA at 415 V and 440 V, 121 kA at 500 V, and 5 kA at 690 V — the 242 kA figure is the headline number for sizing against high available fault current at the service entrance or large transformer secondary. The breaker holds 100 A continuously from 40 °C through 50 °C ambient, then derates linearly to 85 A at 70 °C (the maximum operating ambient). That means in a hot panel — say a poorly ventilated enclosure near a furnace line or in a Middle East outdoor cabinet — the 100 A frame still delivers 92.5 A at 60 °C and 88.75 A at 65 °C, which is better than many frames that start derating at 40 °C. ## Auxiliary contacts and trip signaling The integrated auxiliary trip module is order code 3VA9688-0BL30; the supplied basic switch is 3VA2110-6HN36-0AA0. No undervoltage release, no ground fault monitoring, no communication function or phase failure detection — this is a straightforward line-protection MCCB with remote trip capability and status feedback for a PLC or SCADA system. The 105 mm width (about 4.1 inches) matches the 3VA2 frame footprint; if you are replacing a 3VA1 or older 3VL frame, verify the mounting hole pattern and busbar spacing before committing the panel layout.","metaTitle":"Siemens 3VA2110-6HN36-0HH0 SENTRON MCCB, 100 A, 242 kA at 24","metaDescription":"Siemens SENTRON 3VA2110-6HN36-0HH0 molded case circuit breaker, 100 A rated, 242 kA interrupting at 240 V. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96.25 A","at 60 °C":"92.5 A","at 65 °C":"88.75 A","at 70 °C":"85 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"10 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2110-6HN36-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL30","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.4 s","Adjustable response value time / tsd min.":"0.02 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 200 A","Adjustable response value current / li min.":"1 200 A","Adjustable response value current / lr min.":"40 A","Adjustable response value current / Isd max.":"1 000 A","Adjustable response value current / Isd min.":"150 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (6-120 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=127472&mlfb=3VA2110-6HN36-0HH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HN36-0HH0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting capacity of 3VA2110-6HN36-0HH0 at 240 V?","answer":"242 kA at 240 V AC, which is the highest interrupting rating in the 3VA2 frame range and suitable for service-entrance or high-fault panels."},{"question":"What is the closest functional second-source to 3VA2110-6HN36-0HH0?","answer":"The 3VA1110-5EE32-0JA0 is a 3-pole SENTRON MCCB but with a lower interrupting rating and different release (ETU320 vs ETU350). It will not drop into the same panel without verifying the mounting footprint and busbar spacing — the 3VA1 frame shares the same 105 mm width but has different depth and terminal arrangements. Always confirm the physical fit and coordination study before substituting."},{"question":"Where can I buy 3VA2110-6HN36-0HH0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-6HN36-0HH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-6HN36-0HH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}