{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-6HN36-0JH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-6HN36-0JH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-6HN36-0JH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HN36-0JH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-6HN36-0JH0, molded case circuit breaker, 3-pole, 100 A continuous, line protection, shunt trip + 2 aux switches + 1 trip alarm, 86 mm depth.","salesMarkdown":"Three poles, line-protection design, which means it's sized for feeder or main distribution duty in a panel, not motor branch-circuit protection. Interrupting capacity hits 242 kA at 240 V, 187 kA at 415 V, and still 121 kA at 500 V; that's enough for high-fault industrial services without cascading upstream breakers. No communication module onboard — this is a standalone breaker, not a power-metering or fieldbus device. Standard MCCB footprint for a 100 A frame — fits a typical distribution panel's bolted mounting plate or draw-out cradle. Power loss is 10 W max at rated load — negligible heat contribution for a 100 A breaker, but factor it if you're packing multiple units in a sealed stainless-steel cabinet.","metaTitle":"Siemens 3VA2110-6HN36-0JH0 SENTRON MCCB, 100 A, 3-Pole","metaDescription":"Siemens 3VA2110-6HN36-0JH0 SENTRON molded case circuit breaker, 100 A continuous, 3-pole, 242 kA at 240 V interrupting rating. Line protection with shunt trip. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"1 200 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3.7 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21106HN360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=273260&mlfb=3VA2110-6HN36-0JH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6HN36-0JH0/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for 3VA2110-6HN36-0JH0?","answer":"Continuous current is 100 A (no derating from 40 °C to 70 °C). Interrupting capacity: 242 kA at 240 V, 187 kA at 415 V, 121 kA at 500 V, 3.7 kA at 690 V. Three poles, line-protection design, with shunt trip release and two auxiliary switches plus one trip alarm."},{"question":"What is the depth of 3VA2110-6HN36-0JH0?","answer":"Depth is 86 mm (3.39 in). Height is 181 mm (7.13 in), width is 105 mm (4.13 in)."},{"question":"Where can I buy 3VA2110-6HN36-0JH0 and get current pricing?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer."},{"question":"Does 3VA2110-6HN36-0JH0 have a shunt trip?","answer":"Yes, it includes a shunt trip (STL) auxiliary release for remote tripping. Also has two auxiliary switches and one trip-alarm switch (HQ) for status indication."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-6HN36-0JH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-6HN36-0JH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}