{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-6KP36-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-6KP36-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-6KP36-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6KP36-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-6KP36-0AA0, 3-pole molded case circuit breaker, 100 A continuous, ETU850 electronic trip unit, 242 kA at 240 V, line protection design with communication function.","salesMarkdown":"It carries an ETU850 electronic trip unit with communication capability, so it can report status and trip events over a network — useful for a plant-floor SCADA or a BMS that needs to know which breaker opened without sending someone to look. The interrupting ratings are what make this breaker fit for high-fault locations: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3.7 kA at 690 V. That 242 kA at 240 V is the number that matters for most North American 277/480 V panels where the available fault current can push past 200 kA on the secondary of a large transformer. The 3.7 kA at 690 V tells you this is not a 690 V workhorse — it's a 240–500 V breaker. The adjustable current range runs from 150 A minimum to 1 200 A maximum, which is the setting window for the ETU850 trip unit. That means you can dial the long-time pickup anywhere in that band to match the load cable or transformer — you are not stuck at the 100 A frame rating. The continuous rating of 100 A is the frame's thermal limit; the trip unit settings govern the actual protection threshold. Front protection is IP40, so it keeps out tools and fingers but not water. Power loss is 10 W maximum at rated current. That is low enough to skip forced cooling in a ventilated panel, but if you are packing ten of these in a sealed cabinet, add up the heat and plan for it. ## Environmental limits and storage","metaTitle":"Siemens SENTRON 3VA2110-6KP36-0AA0 MCCB, 100 A, 1200 A max,","metaDescription":"Siemens SENTRON 3VA2110-6KP36-0AA0 molded case circuit breaker, 3-pole, 100 A continuous, ETU850 trip unit, 242 kA at 240 V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"3.7 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU850","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=15552&mlfb=3VA2110-6KP36-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-6KP36-0AA0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-6KP36-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-6KP36-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}