{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-7JQ36-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-7JQ36-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-7JQ36-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-7JQ36-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-7JQ36-0AA0, molded case circuit breaker, 3-pole, 100 A continuous, line protection, interrupting 330 kA at 240 V, 242 kA at 415 V.","salesMarkdown":"Three poles, rated insulation voltage 800 V, and interrupting capacity that reaches 330 kA at 240 V, 242 kA at 415 V, and 187 kA at 500 V. Dimensions: 86 mm depth, 105 mm width, 181 mm height. The 3-pole footprint matches standard SENTRON 3VA2 cutouts; verify the 105 mm width against your existing busbar spacing or enclosure gland plate. The initial trip setting is 20 A, so the breaker will not hold below that threshold — confirm your minimum load current exceeds 20 A. Communication function is present, enabling remote monitoring or trip indication via the SENTRON bus system. No undervoltage release or trip indicator is fitted on this variant.","metaTitle":"Siemens 3VA2110-7JQ36-0AA0 SENTRON MCCB, 100 A, 3-Pole, 240","metaDescription":"Siemens 3VA2110-7JQ36-0AA0 SENTRON molded case circuit breaker, 100 A continuous, 3-pole, interrupting 330 kA at 240 V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"3.7 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Initial Value":"20 A","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Full-Scale Value":"100 A","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Summation current formation L-conductor","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU560","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Product Function / Grounding Protection":"Yes","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSIG","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"C","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=217564&mlfb=3VA2110-7JQ36-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-7JQ36-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2110-7JQ36-0AA0?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What are the key ratings of 3VA2110-7JQ36-0AA0?","answer":"Continuous current 100 A, 3-pole, rated insulation voltage 800 V. Interrupting capacity: 330 kA at 240 V, 242 kA at 415 V, 242 kA at 440 V, 187 kA at 500 V, 3.7 kA at 690 V. No derating from 40 °C to 70 °C."},{"question":"What is the physical size of 3VA2110-7JQ36-0AA0?","answer":"Depth 86 mm, width 105 mm, height 181 mm. Fits standard SENTRON 3VA2 panel cutouts and DIN-rail mounting."},{"question":"Does 3VA2110-7JQ36-0AA0 have communication capability?","answer":"Yes, it includes a communication function for remote monitoring or trip indication via the SENTRON bus system."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-7JQ36-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-7JQ36-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}