{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-7MN32-0HC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-7MN32-0HC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-7MN32-0HC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-7MN32-0HC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA2 IEC frame 160, breaking capacity class C, Icu=110kA @ 415V, 3-pole, motor protection ETU350M, LSI, In=100A, overload Ir=40-100A, shunt trip 12-30V DC / 24V AC, 2 aux switches HQ.","salesMarkdown":"The Siemens 3VA2110-7MN32-0HC0 is a 3-pole IEC frame 160 circuit breaker with a 110 kA breaking capacity at 415 V — class C, meaning it clears high-fault-current events on industrial motor circuits without upstream coordination headaches. The ETU350M trip unit gives you LSI protection (Long-time, Short-time, Instantaneous) with an overload range Ir = 40 A to 100 A and short-circuit pickup Isd = 3 to 15 × Ir. Instantaneous fixed at Ii = 15 × In (1500 A at the 100 A rating). That Ii setting is deliberate for motor starting inrush: it rides through the start transient and only trips on a bolted fault. Two auxiliary switches (HQ) report breaker position back to the control system. We quote the 3VA2110-7MN32-0HC0 to order against an RFQ. Same part, different passport — genuine Siemens hardware, no region-lock issues. The frame 160 footprint is compact for the 110 kA rating — leaves room for downstream contactors and overload relays in a motor control center bucket. The included nut keeper kit saves a step during terminal tightening.","metaTitle":"Siemens 3VA2110-7MN32-0HC0 Circuit Breaker, 110kA @ 415V, 10","metaDescription":"Siemens 3VA2110-7MN32-0HC0 IEC frame 160 circuit breaker, 110kA breaking capacity at 415V, 100A, motor protection ETU350M, LSI. Current lifecycle stage. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=569424&mlfb=3VA2110-7MN32-0HC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-7MN32-0HC0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this breaker?","answer":"Icu = 110 kA at 415 V AC, breaking capacity class C per IEC 60947-2. That rating covers high-fault industrial motor circuits."},{"question":"Where can I buy the 3VA2110-7MN32-0HC0?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-7MN32-0HC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-7MN32-0HC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}