{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-7MN36-0AH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-7MN36-0AH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-7MN36-0AH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-7MN36-0AH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-7MN36-0AH0, molded case circuit breaker, 3-pole, 100 A, motor protection version, ETU350M electronic release, 330 kA interrupting at 240 V.","salesMarkdown":"It uses the ETU350M electronic overcurrent release with phase-failure detection built in. The continuous current holds at 100 A from 40 °C up to 50 °C ambient, then derates to 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C. The maximum power loss is 75 W, so factor that into the enclosure thermal budget. The width of 105 mm is standard for a 3-pole 100 A frame in the SENTRON 3VA line.","metaTitle":"Siemens 3VA2110-7MN36-0AH0 SENTRON MCCB, 100 A, 330 kA","metaDescription":"Siemens SENTRON 3VA2110-7MN36-0AH0 molded case circuit breaker, 3-pole, 100 A rated, 330 kA at 240 V. Motor protection version with ETU350M release. Current production. Sourced to","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"52.5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96 A","at 60 °C":"94 A","at 65 °C":"92 A","at 70 °C":"90 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Motor protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"75 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2110-7MN36-0AA0","Design of the auxiliary release":"Without auxiliary release","Ground fault monitoring version":"Without","Design of the overcurrent release":"ETU350M","Protection class IP / on the front":"IP40","Operating power / at AC-3 / at 400 V":"45 W","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"4","Adjustable response value time / tsd max.":"0.03 s","Adjustable response value time / tsd min.":"0.03 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 500 A","Adjustable response value current / li min.":"1 500 A","Adjustable response value current / lr min.":"40 A","Adjustable response value current / Isd max.":"1 500 A","Adjustable response value current / Isd min.":"300 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"C","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=569442&mlfb=3VA2110-7MN36-0AH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-7MN36-0AH0/alternatives.json"},"ai":{"faq":[{"question":"What is 3VA2110-7MN36-0AH0's listed depth?","answer":"The depth is 86 mm from the mounting surface to the front of the breaker."},{"question":"Will 3VA2110-7MN36-0AH0 drop into a panel specified around a similar 3VA frame breaker?","answer":"Yes, the 105 mm width is common across the 3VA1 and 3VA2 frames at this rating, so the footprint matches without bus-bar or wiring changes."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-7MN36-0AH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-7MN36-0AH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}