{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-7MN36-0CC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-7MN36-0CC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-7MN36-0CC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-7MN36-0CC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-7MN36-0CC0, molded case circuit breaker, motor protection design, 3-pole, 100 A, interrupting capacity 330 kA at 240 V, 86 mm depth, 105 mm width, 181 mm height.","salesMarkdown":"The interrupting capacity hits 330 kA at 240 V and stays strong at 242 kA up through 440 V, dropping to 187 kA at 500 V and 3.7 kA at 690 V. That's enough fault current for most industrial service-entrance and distribution panels. That matters when this breaker sits in a crowded enclosure next to drives or transformers that push ambient air well past 40 °C. The interrupting capacities are given at specific voltages: at 240 V it clears 330 kA, at 415/440 V it clears 242 kA, at 500 V it clears 187 kA, and at 690 V it clears 3.7 kA. That 3.7 kA figure at 690 V is the weak point — if your system runs 690 V with available fault current above that, you need a different frame. For standard 480 V distribution the 187 kA is more than adequate behind a transformer. The 105 mm width (4.13 in) is the standard 3-pole MCCB footprint for this SENTRON frame — it fits the same panel cutout and DIN-rail adapter as other 3VA2 units. The 86 mm depth (3.39 in) leaves room for rear-connection terminals and cable bending radius inside the enclosure.","metaTitle":"Siemens 3VA2110-7MN36-0CC0 SENTRON MCCB, 100 A, 3-Pole, Moto","metaDescription":"Siemens 3VA2110-7MN36-0CC0 SENTRON molded case circuit breaker, 100 A rated current, 3-pole motor protection, interrupting capacity up to 330 kA at 240 V. Active production, source","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"17 s","Minimum":"4 s","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"3.7 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Motor protection","Communication Function":"No","Phase Failure Detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"12.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21107MN360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","adjustable trip class (Tc CLASS)":"10A, 10E, 20E","Design Of The Overcurrent Release":"ETU350M","protection class IP / on the front":"IP40","operating power / at AC-3 / at 230 V":"30 000 W","operating power / at AC-3 / at 400 V":"55 000 W","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB24","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"C","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=569449&mlfb=3VA2110-7MN36-0CC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-7MN36-0CC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2110-7MN36-0CC0?","answer":"This MCCB is available through independent distribution. Submit an RFQ for current pricing and lead time — availability is confirmed at quote time."},{"question":"What is the interrupting capacity of 3VA2110-7MN36-0CC0 at 480 V?","answer":"The interrupting capacity is 187 kA at 500 V, which covers 480 V systems. At 240 V it is 330 kA, at 415/440 V it is 242 kA, and at 690 V it is 3.7 kA."},{"question":"Does 3VA2110-7MN36-0CC0 include undervoltage release and auxiliary switches?","answer":"Yes, it comes with an undervoltage release (UVR) and two HQ auxiliary switches factory-installed."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-7MN36-0CC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-7MN36-0CC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}