{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-7MN36-0DC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-7MN36-0DC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-7MN36-0DC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-7MN36-0DC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-7MN36-0DC0, 3-pole molded case circuit breaker, motor protection, 100 A rated continuous current, ETU350M electronic trip unit, 330 kA interrupting at 240 V.","salesMarkdown":"At 70 °C ambient it still carries 90 A — useful for a crowded panel where the internal temperature runs high. Interrupting capacity is 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 52.5 kA at 690 V. That 330 kA figure at 240 V covers high-fault locations like a transformer secondary or a large UPS bypass; the 52.5 kA at 690 V is still substantial for most industrial 690 V distribution. Dimensions are 105 mm wide, 181 mm high, 86 mm deep — a standard SENTRON 3VA2 footprint that fits the same DIN-rail or screw-mount pattern as the rest of the 3VA2 family. Maximum power loss is 75 W — factor that into the panel thermal budget if you are grouping several breakers in a sealed enclosure. The 3VA2110-7MN36-0DC0 ships with 2 auxiliary switches (HQ type) pre-installed — order code 3VA9608-0BB25 for the auxiliary trip block. The undervoltage release (UVR) is integrated, so no separate coil wiring is needed for remote shunt-trip capability. The part carries a CE marking for the European market.","metaTitle":"Siemens 3VA2110-7MN36-0DC0 SENTRON MCCB, 100 A, 330 kA at 24","metaDescription":"Siemens 3VA2110-7MN36-0DC0 SENTRON molded case circuit breaker, 3-pole, 100 A, ETU350M release, 330 kA at 240 V. Current lifecycle, sourced to order. RFQ for pricing.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"52.5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96 A","at 60 °C":"94 A","at 65 °C":"92 A","at 70 °C":"90 A","Trip indicator":"No","Number of poles":"3","Product version":"Motor protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"75 W","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2110-7MN36-0AA0","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB25","Design of the overcurrent release":"ETU350M","Protection class IP / on the front":"IP40","Operating power / at AC-3 / at 400 V":"45 W","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"4","Adjustable response value time / tsd max.":"0.03 s","Adjustable response value time / tsd min.":"0.03 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 500 A","Adjustable response value current / li min.":"1 500 A","Adjustable response value current / lr min.":"40 A","Adjustable response value current / Isd max.":"1 500 A","Adjustable response value current / Isd min.":"300 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"C","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=569453&mlfb=3VA2110-7MN36-0DC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-7MN36-0DC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2110-7MN36-0DC0 and how is it quoted?","answer":"We source it through independent distribution and quote it to order against an RFQ. Availability and current pricing are confirmed at quote time."},{"question":"What is the closest functional second-source for 3VA2110-7MN36-0DC0?","answer":"The 3VA1112-5EF32-0CA0 is a 3-pole SENTRON MCCB with a different trip unit (ETU320 vs ETU350M) and lower interrupting capacity. It shares the same 105 mm width and 181 mm height, so it can drop into the same panel cutout, but the trip curve and protection functions differ — verify coordination before substituting."},{"question":"What is the depth of 3VA2110-7MN36-0DC0?","answer":"The depth is 86 mm."},{"question":"What is the width of 3VA2110-7MN36-0DC0?","answer":"The width is 105 mm."},{"question":"Will 3VA2110-7MN36-0DC0 drop into a panel specified around 3VA1112-5EF32-0CA0?","answer":"Yes — both share the same 105 mm width, 181 mm height, and 3-pole form factor, so the mechanical fit is identical. No rewiring of the busbar or DIN-rail mount is needed."},{"question":"What compliance documentation does this part carry?","answer":"Standard SENTRON documentation includes RoHS, REACH, and CE marking. UL and IEC certification data is available on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-7MN36-0DC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-7MN36-0DC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}