{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-7MP36-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-7MP36-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-7MP36-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-7MP36-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-7MP36-0AA0, molded case circuit breaker, 3-pole, 100 A rated continuous current, motor protection design, adjustable trip class, 330 kA breaking capacity at 240 VAC.","salesMarkdown":"The Siemens 3VA2110-7MP36-0AA0 is a 3-pole SENTRON molded case circuit breaker rated for 100 A continuous current across its full ambient range — no derating needed from 40 °C up through 70 °C, which simplifies panel layout when the breaker sits near other heat sources. It is purpose-built for motor protection, with an adjustable trip class that lets you set the overload curve to match the starting characteristics of the connected load — selectable between CLASS 10A, 10/10E, 20/20E, or 30/30E. Breaking capacity reaches 330 kA at 240 VAC, dropping to 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3.7 kA at 690 V — numbers that matter when coordinating with upstream transformers or generators in a high-fault installation. Built-in phase failure detection and a communication function allow the breaker to report status and trip events to a PLC or SCADA system, cutting down on manual troubleshooting for a remote motor line. Operates from -25 °C to 70 °C ambient and survives storage from -40 °C to 80 °C; maximum power loss is 10 W, so ventilation requirements in a sealed enclosure are modest.","metaTitle":"Siemens 3VA2110-7MP36-0AA0 SENTRON MCCB, 100 A, 3-Pole, 330","metaDescription":"Siemens SENTRON 3VA2110-7MP36-0AA0 molded case circuit breaker, 100 A continuous, 3-pole, 330 kA breaking capacity at 240 VAC. Motor protection design with adjustable trip class an","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"25 s","Minimum":"3 s","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"3.7 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Motor protection","Communication Function":"Yes","Phase Failure Detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","adjustable trip class (Tc CLASS)":"10A, 10/10E, 20/ 20E, 30/30E","Design Of The Overcurrent Release":"ETU550M","protection class IP / on the front":"IP40","operating power / at AC-3 / at 230 V":"30 000 W","operating power / at AC-3 / at 400 V":"55 000 W","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"C","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1133433&mlfb=3VA2110-7MP36-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-7MP36-0AA0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA2110-7MP36-0AA0?","answer":"Submit an RFQ through this listing. Pricing and stock are confirmed at quote time through the independent distribution channel."},{"question":"What is the breaking capacity of 3VA2110-7MP36-0AA0 at different voltages?","answer":"At 240 VAC it is 330 kA; at 415 V and 440 V it is 242 kA; at 500 V it is 187 kA; at 690 V it is 3.7 kA."},{"question":"What compliance documentation does this brand provide for 3VA2110-7MP36-0AA0?","answer":"The SENTRON series typically carries UL, IEC, CSA, and CE certifications; RoHS and REACH declarations are available through Siemens documentation. Verify the specific certification markings on the unit or request the declaration of conformity with your order."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-7MP36-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-7MP36-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}