{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-7MS36-0AG0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-7MS36-0AG0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-7MS36-0AG0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-7MS36-0AG0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-7MS36-0AG0, molded case circuit breaker, 3-pole, 100 A, breaking capacity 330 kA at 240 V, ETU310M electronic trip unit.","salesMarkdown":"The Siemens SENTRON 3VA2110-7MS36-0AG0 is a 3-pole molded case circuit breaker rated for a continuous current of 100 A across the full 40 °C to 70 °C ambient range — no derating needed up to that temperature, which simplifies panel thermal budgeting. At 690 V the breaking capacity drops to 3.7 kA — that's the limit for 690 V line-to-line circuits, so if you're feeding a 690 V motor drive, verify the fault current at that point doesn't exceed this value. ## Starter protection version — what that means on the line This is the starter protection version of the 3VA2 frame, meaning it's configured for motor branch-circuit protection with the ETU310M release tuned for motor-starting inrush and overload profiles. Out here in the grease on a rotating-equipment route, that trip alarm is what tells you a motor locked rotor or a phase imbalance took out the breaker before you walk the whole line. ## Physical fit — dimensions for panel layout That 105 mm width for a 3-pole 100 A MCCB is standard for the SENTRON 3VA2 frame, so it drops into the same DIN-rail or mounting-plate footprint as other 3VA2 breakers. The 86 mm depth keeps the body behind the panel door without interfering with gland plates or busbar shrouds in most enclosures.","metaTitle":"Siemens 3VA2110-7MS36-0AG0 MCCB, 100 A, 330 kA at 240 V","metaDescription":"Siemens SENTRON 3VA2110-7MS36-0AG0 molded case circuit breaker, 100 A rated current, 330 kA breaking capacity at 240 V. 3-pole, ETU310M release. Current production. Quoted to order","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"3.7 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Product version":"Starter protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"No","Phase Failure Detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10 W","Auxiliary contact version":"1 auxiliary switch + 1 trip alarm switch HP","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21107MS360AA0","Courant permanent assigné Iu":"100 A","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU310M","protection class IP / on the front":"IP40","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"I","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB11","Switching Capacity Class Of The Circuit Breaker":"C","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=569593&mlfb=3VA2110-7MS36-0AG0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-7MS36-0AG0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2110-7MS36-0AG0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution, with availability and current pricing confirmed at quote time."},{"question":"What is 3VA2110-7MS36-0AG0's listed depth?","answer":"The depth is 86 mm."},{"question":"What is 3VA2110-7MS36-0AG0's listed width?","answer":"The width is 105 mm."},{"question":"Will 3VA2110-7MS36-0AG0 drop into a panel specified around 3VA2110-8HN32-0AA0 without rewiring?","answer":"Both breakers share the same 3VA2 frame dimensions (105 mm wide, 181 mm high, 86 mm deep), so the physical footprint is identical. The difference is in the trip unit and ratings — verify the 100 A continuous rating and ETU310M release match your coordination study before swapping."},{"question":"What compliance documentation does this brand provide for 3VA2110-7MS36-0AG0?","answer":"Siemens SENTRON MCCBs carry UL, CSA, and IEC certifications per the product family standards. Specific compliance declarations (RoHS, REACH, CE, UKCA) are available from the manufacturer's documentation portal for this order code."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-7MS36-0AG0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-7MS36-0AG0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}