{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-7MS36-0BL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-7MS36-0BL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-7MS36-0BL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-7MS36-0BL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-7MS36-0BL0, molded case circuit breaker, 3-pole, 100 A, interrupting 330 kA at 240 V, starter protection design, undervoltage release.","salesMarkdown":"Interrupting capacity hits 330 kA at 240 V, 242 kA at 415 V, and still 187 kA at 500 V; at 690 V it drops to 3.7 kA — that last number tells you this breaker is sized for 400 V class distribution, not 690 V motor feeders. Three poles, 300 A minimum to 1 500 A maximum frame rating — the 100 A thermal-magnetic trip is set at the factory. Undervoltage release (UVR) is built in, so if your control voltage drops, the breaker opens without a separate shunt trip module.","metaTitle":"Siemens 3VA2110-7MS36-0BL0 SENTRON MCCB, 100 A, 240V 330 kA","metaDescription":"Siemens 3VA2110-7MS36-0BL0 SENTRON molded case circuit breaker, 100 A rated, 3-pole, 240V 330 kA interrupting, starter protection, undervoltage release. Active production, sourced","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 500 A","Minimum":"300 A","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"3.7 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Starter protection","Communication Function":"No","Phase Failure Detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"12.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21107MS360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU310M","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB11","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"I","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"C","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=569599&mlfb=3VA2110-7MS36-0BL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-7MS36-0BL0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting capacity of 3VA2110-7MS36-0BL0 at 240 V?","answer":"330 kA at 240 V. At 415 V and 440 V it's 242 kA; at 500 V it's 187 kA; at 690 V it drops to 3.7 kA. That 690 V number is the weak point — this breaker is designed for 400 V class distribution, not 690 V motor feeders."},{"question":"What is the continuous current rating and does it derate with temperature?","answer":"100 A continuous from 40 °C all the way up to 70 °C — no derating needed across that entire operating range. That's unusual for an MCCB; most start losing capacity above 40 °C."},{"question":"Where can I buy 3VA2110-7MS36-0BL0 and how is it quoted?","answer":"Sourced and quoted to order through independent industrial distribution. Submit an RFQ for current pricing and availability — confirmed at quote time, not before."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-7MS36-0BL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-7MS36-0BL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}