{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-7MS36-0CC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-7MS36-0CC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-7MS36-0CC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-7MS36-0CC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON, Molded case circuit breaker, 3VA2110-7MS36-0CC0, 3-pole, 100 A, starter protection version with ETU310M trip unit, 330 kA at 240 V.","salesMarkdown":"The Siemens 3VA2110-7MS36-0CC0 is a SENTRON molded case circuit breaker (MCCB) in the starter protection product version, rated for a continuous current Iu of 100 A across a 40 °C to 50 °C ambient band — it holds 100 A flat through that range, then derates to 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C. That thermal profile means the breaker can be installed in a warm panel without oversizing, as long as the ambient stays under 50 °C at full load. Breaking capacity is the headline: 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 52.5 kA at 690 V. It is a 3-pole unit with an ETU310M electronic overcurrent release. The 'M' suffix on the release designates motor / starter protection characteristics, meaning it provides the Class 10 or Class 20 overload curve needed for motor starting inrush without nuisance tripping. ## Built-in auxiliary and undervoltage release The auxiliary switches are wired for status feedback — open/closed indication to a PLC or status lamp. The integrated auxiliary trip is 3VA9608-0BB24 — these are the internal sub-assembly order codes if you need replacement parts. Physical dimensions: 181 mm height, 105 mm width, 86 mm depth — standard SENTRON 3VA2 frame size.","metaTitle":"Siemens 3VA2110-7MS36-0CC0 SENTRON MCCB, 100A, 330kA at 240V","metaDescription":"Siemens 3VA2110-7MS36-0CC0 SENTRON molded case circuit breaker, 100 A, 3-pole, starter protection, ETU310M trip unit, 330 kA at 240 V. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"52.5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96 A","at 60 °C":"94 A","at 65 °C":"92 A","at 70 °C":"90 A","Trip indicator":"No","Number of poles":"3","Product version":"Starter protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"75 W","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2110-7MS36-0AA0","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB24","Design of the overcurrent release":"ETU310M","Protection class IP / on the front":"IP40","Operating power / at AC-3 / at 400 V":"45 W","Reference code / acc. to DIN EN 81346-2":"Q","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"0 A","Adjustable response value current / li max.":"1 500 A","Adjustable response value current / li min.":"300 A","Adjustable response value current / lr min.":"0 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"I","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"C","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=569601&mlfb=3VA2110-7MS36-0CC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-7MS36-0CC0/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for 3VA2110-7MS36-0CC0?","answer":"Rated continuous current Iu of 100 A, 3-pole, breaking capacity of 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 52.5 kA at 690 V. It uses an ETU310M electronic overcurrent release for motor/starter protection."},{"question":"Where can I buy 3VA2110-7MS36-0CC0 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is the depth of 3VA2110-7MS36-0CC0?","answer":"The depth is 86 mm. Overall dimensions are 181 mm height by 105 mm width by 86 mm depth."},{"question":"Will 3VA2110-7MS36-0CC0 drop into a panel specified for 3VA2110-7HK42-0AA0?","answer":"Both are 3VA2 frame SENTRON MCCBs sharing the same 181 x 105 x 86 mm footprint and DIN-rail mounting pattern, so mechanical fit is identical. The difference is in the trip unit and accessories — verify the 7HK42 variant's continuous current and release type match your coordination study before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-7MS36-0CC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-7MS36-0CC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}