{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-7MS36-0DA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-7MS36-0DA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-7MS36-0DA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-7MS36-0DA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-7MS36-0DA0, molded case circuit breaker, 3-pole, 100 A rated continuous current, 330 kA breaking capacity at 240 V, starter protection version with ETU310M electronic release and undervoltage release.","salesMarkdown":"## Integrator's note — 3VA2110-7MS36-0DA0 The Siemens SENTRON 3VA2110-7MS36-0DA0 is a 3-pole molded case circuit breaker rated for 100 A continuous current at 40 °C, with a breaking capacity of 330 kA at 240 V and 242 kA at 415 V. This is the starter protection variant, fitted with an ETU310M electronic overcurrent release and an integrated undervoltage release (UVR). The 330 kA at 240 V and 242 kA at 415 V place this breaker in the high-interrupting category for a 100 A frame. For selectivity studies, the ETU310M release provides adjustable overload and short-circuit pickup, allowing coordination with downstream breakers in a distribution panel. The 800 V rated insulation voltage (Ui) supports 690 V line-to-line systems, where the breaking capacity drops to 52.5 kA — still adequate for most industrial 690 V bus feeds. The breaker carries 100 A continuously up to 50 °C ambient, then derates to 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C. Maximum power loss is 75 W.","metaTitle":"Siemens 3VA2110-7MS36-0DA0 SENTRON MCCB, 100 A, 330 kA at 24","metaDescription":"Siemens SENTRON 3VA2110-7MS36-0DA0 molded case circuit breaker, 100 A rated, 330 kA breaking at 240 V. Starter protection version with ETU310M release. Current production. Availabl","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"52.5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96 A","at 60 °C":"94 A","at 65 °C":"92 A","at 70 °C":"90 A","Trip indicator":"No","Number of poles":"3","Product version":"Starter protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"75 W","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2110-7MS36-0AA0","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB25","Design of the overcurrent release":"ETU310M","Protection class IP / on the front":"IP40","Operating power / at AC-3 / at 400 V":"45 W","Reference code / acc. to DIN EN 81346-2":"Q","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"0 A","Adjustable response value current / li max.":"1 500 A","Adjustable response value current / li min.":"300 A","Adjustable response value current / lr min.":"0 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"I","Switching capacity class of the circuit breaker":"C","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=569604&mlfb=3VA2110-7MS36-0DA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-7MS36-0DA0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2110-7MS36-0DA0 at different voltages?","answer":"330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 52.5 kA at 690 V."},{"question":"What overcurrent release does this breaker use?","answer":"It uses the ETU310M electronic release, which provides adjustable overload and short-circuit protection settings."},{"question":"Does 3VA2110-7MS36-0DA0 include an undervoltage release?","answer":"Yes, it is factory-fitted with an undervoltage release (UVR) as the auxiliary release."},{"question":"Where can I buy 3VA2110-7MS36-0DA0?","answer":"This part is sourced and quoted to order against an RFQ through independent industrial distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-7MS36-0DA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-7MS36-0DA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}