{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-7MS36-0HA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-7MS36-0HA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-7MS36-0HA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-7MS36-0HA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-7MS36-0HA0, molded case circuit breaker, 3-pole, 100 A rated continuous current, 330 kA interrupting capacity at 240 V, starter protection version with ETU310M electronic trip unit and shunt trip release.","salesMarkdown":"At 415 V and 440 V it still holds 242 kA, and at 690 V it is rated 52.5 kA. The ETU310M electronic overcurrent release gives it adjustable long-time, short-time, and instantaneous pickup settings — not just a fixed thermal-magnetic curve. That matters when you are protecting a motor: you can set the long-time pickup to ride through the inrush without nuisance tripping, and the short-time delay lets you coordinate with downstream starters or contactors. The shunt trip release (STL) allows remote tripping from an E-stop or PLC output, which is standard for safety circuits. No undervoltage release is fitted, so the breaker stays latched on loss of control power — a deliberate choice if you do not want the line to drop on a brownout. ## Current ratings and thermal derating — the real continuous capability At 55 °C it drops to 96 A, at 60 °C to 94 A, at 65 °C to 92 A, and at 70 °C to 90 A (–). ## Physical fit — panel dimensions and mounting No special adapter plate needed for a typical 600 mm wide distribution panel.","metaTitle":"Siemens SENTRON 3VA2110-7MS36-0HA0 MCCB, 100 A, 330 kA at 24","metaDescription":"Siemens SENTRON 3VA2110-7MS36-0HA0 molded case circuit breaker, 3-pole, 100 A, 330 kA interrupting at 240 V. Starter protection version with ETU310M release. Current production. So","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"52.5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96 A","at 60 °C":"94 A","at 65 °C":"92 A","at 70 °C":"90 A","Trip indicator":"No","Number of poles":"3","Product version":"Starter protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"75 W","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2110-7MS36-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL30","Design of the overcurrent release":"ETU310M","Protection class IP / on the front":"IP40","Operating power / at AC-3 / at 400 V":"45 W","Reference code / acc. to DIN EN 81346-2":"Q","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"0 A","Adjustable response value current / li max.":"1 500 A","Adjustable response value current / li min.":"300 A","Adjustable response value current / lr min.":"0 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"I","Switching capacity class of the circuit breaker":"C","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=569608&mlfb=3VA2110-7MS36-0HA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-7MS36-0HA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2110-7MS36-0HA0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is the closest functional second-source to 3VA2110-7MS36-0HA0?","answer":"Within the SENTRON 3VA family, the 3VA1110-5EE32-0JA0 is a 3-pole 100 A MCCB but in a standard distribution version, not starter protection, and without the shunt trip or ETU310M release. It will not drop into a panel wired for the shunt trip without rewiring the control circuit. The 3VA2110-7MS36-0HA0 is the correct part for motor branch protection with remote trip capability."},{"question":"What is the depth of 3VA2110-7MS36-0HA0?","answer":"The depth is 86 mm. This is the dimension from the mounting surface to the front of the breaker, excluding any protruding trip unit or auxiliary modules."},{"question":"What is the width of 3VA2110-7MS36-0HA0?","answer":"The width is 105 mm. This is the standard 3-pole frame width for the SENTRON 3VA series."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-7MS36-0HA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-7MS36-0HA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}