{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-7MS36-0JA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-7MS36-0JA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-7MS36-0JA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-7MS36-0JA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-7MS36-0JA0, molded case circuit breaker, 3-pole, 100 A continuous, with shunt trip (STL), interrupting capacity 330 kA at 240 V AC.","salesMarkdown":"This breaker carries a symmetrical interrupting capacity of 330 kA at 240 V AC, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3.7 kA at 690 V. The 690 V figure is notably lower — that's the voltage class where the arc extinction physics changes for this frame size; it still clears a fault, but the available fault current must be limited to under 3.7 kA at that voltage. For most 400 V-class industrial panels, the 242 kA rating provides ample margin even on high-capacity transformer secondaries.","metaTitle":"Siemens 3VA2110-7MS36-0JA0 SENTRON MCCB, 100 A, 3-pole, shun","metaDescription":"Siemens 3VA2110-7MS36-0JA0 SENTRON molded case circuit breaker, 100 A continuous, 3-pole, 330 kA at 240 V. Active production. Quoted to order. Request RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 500 A","Minimum":"300 A","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"3.7 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Starter protection","Communication Function":"No","Phase Failure Detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21107MS360AA0","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU310M","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"I","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"C","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=569612&mlfb=3VA2110-7MS36-0JA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-7MS36-0JA0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA2110-7MS36-0JA0?","answer":"Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels."},{"question":"Will 3VA2110-7MS36-0JA0 drop into a panel specified around 3VA2116-5JP32-0AE0 without rewiring?","answer":"The 3VA2110-7MS36-0JA0 shares the same SENTRON 3VA frame dimensions (181 mm height, 105 mm width, 86 mm depth) as the 3VA2116-5JP32-0AE0, so the physical footprint and mounting pattern are identical. The key difference is the continuous current rating — 100 A on this part versus a higher rating on the 3VA2116 variant — so the branch circuit conductors and upstream protection must be sized for the 100 A rating. No rewiring is needed if the existing conductors are rated for 100 A or less."},{"question":"What compliance documentation does this brand provide for 3VA2110-7MS36-0JA0?","answer":"Siemens SENTRON MCCBs are typically supplied with a declaration of conformity covering IEC 60947-2, and the manufacturer provides RoHS and REACH compliance declarations on request. Specific certification marks (UL, CSA, CE) should be verified against the nameplate marking of the unit received."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-7MS36-0JA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-7MS36-0JA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}