{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-7MS36-0KL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-7MS36-0KL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-7MS36-0KL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-7MS36-0KL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-7MS36-0KL0, molded case circuit breaker, 3-pole, starter protection design, 100 A continuous rating, 330 kA breaking capacity at 240 V, 86 mm depth, 105 mm width, 181 mm height.","salesMarkdown":"Three poles, 100 A continuous at 40 °C all the way up to 70 °C (no derate needed in that band), and a breaking capacity that starts at 330 kA at 240 V and drops to 242 kA at 415/440 V, then 187 kA at 500 V, and 3.7 kA at 690 V. The 100 A rating is flat across the full 40–70 °C ambient range, so you don't lose headroom in a hot enclosure. That's unusual and saves you from having to oversize the frame just because the panel runs warm. That means you get remote trip capability and status feedback without adding external modules. The basic switch order code is 3VA21107MS360AA0 — useful if you're ordering spare switch blocks separately.","metaTitle":"Siemens 3VA2110-7MS36-0KL0 SENTRON MCCB, 100 A, 330 kA at 24","metaDescription":"Siemens SENTRON 3VA2110-7MS36-0KL0 molded case circuit breaker, 100 A continuous, 330 kA breaking at 240 V, 3-pole, starter protection design. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 500 A","Minimum":"300 A","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"3.7 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Starter protection","Communication Function":"No","Phase Failure Detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"10 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21107MS360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU310M","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL33","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"I","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"C","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=569619&mlfb=3VA2110-7MS36-0KL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-7MS36-0KL0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2110-7MS36-0KL0 and get current pricing?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of this MCCB at different voltages?","answer":"330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3.7 kA at 690 V."},{"question":"Does this breaker include a shunt trip or undervoltage release?","answer":"It includes a shunt trip release (STL) but no undervoltage release."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-7MS36-0KL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-7MS36-0KL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}