{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-8JP36-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-8JP36-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-8JP36-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-8JP36-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA series, Molded case circuit breaker, 3VA2110-8JP36-0AA0, 100 A rated current, 3-pole, ETU550 electronic trip unit, breaking capacity 440 kA at 240 V AC.","salesMarkdown":"It carries a breaking capacity of 440 kA at 240 V AC, 330 kA at 415 V and 440 V, 220 kA at 500 V, and 52.5 kA at 690 V — figures that tell you it handles high-fault-current scenarios without cascading failure upstream. IP40 on the front is typical for enclosed panel mount; the breaker itself is not intended for washdown environments. Power loss is 7.7 W maximum, so heat dissipation inside a sealed enclosure is manageable but should be accounted for in the thermal calculation. The ETU550 trip unit supports communication, so you can pull event logs and settings via the SENTRON software suite. No undervoltage release or shunt trip is included; if you need remote tripping, those accessories are ordered separately and install into the breaker's accessory slot.","metaTitle":"Siemens SENTRON 3VA2110-8JP36-0AA0 MCCB, 100 A, 3-Pole, ETU5","metaDescription":"Siemens SENTRON 3VA2110-8JP36-0AA0 molded case circuit breaker, 100 A continuous, 3-pole, ETU550 release, breaking capacity up to 440 kA at 240 V. Active production. Sourced to ord","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"440 kA","at 415 V":"330 kA","at 440 V":"330 kA","at 500 V":"220 kA","at 690 V":"52.5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"7.7 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU550","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"L","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=525834&mlfb=3VA2110-8JP36-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-8JP36-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2110-8JP36-0AA0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of this breaker at different voltages?","answer":"440 kA at 240 V AC, 330 kA at 415 V and 440 V, 220 kA at 500 V, and 52.5 kA at 690 V. These are the maximum interrupting ratings at each voltage level."},{"question":"What trip unit does the 3VA2110-8JP36-0AA0 use?","answer":"It uses the ETU550 electronic trip unit, which provides adjustable long-time, short-time, instantaneous, and ground-fault protection curves for coordination flexibility."},{"question":"Will this breaker fit in a panel designed for a 3VA2010-8HN36-0AA0?","answer":"Both are 3-pole SENTRON 3VA MCCBs with the same physical footprint (105 mm wide, 181 mm high, 86 mm deep), so it will drop into the same mounting position without rewiring. The key difference is the trip unit — the 3VA2110-8JP36-0AA0 carries an ETU550, while the 3VA2010-8HN36-0AA0 uses a different release. Verify the protection settings match your coordination study before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-8JP36-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-8JP36-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}