{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2110-8KP36-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2110-8KP36-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2110-8KP36-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2110-8KP36-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2110-8KP36-0AA0, molded case circuit breaker, 3-pole, 100 A continuous, ETU850 electronic release, line protection, IP40 front, 440 kA at 240 V.","salesMarkdown":"The Siemens SENTRON 3VA2110-8KP36-0AA0 is a 3-pole molded case circuit breaker rated for 100 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. It carries an ETU850 electronic overcurrent release, configurable for line-protection duty, and includes communication capability for integration into a monitored distribution scheme. The interrupting ratings are the headline: 440 kA at 240 V, 330 kA at 415 V and at 440 V, 220 kA at 500 V, and 52.5 kA at 690 V. That puts it in the high-fault tier for industrial mains — think transformer secondaries, large motor control centers, or busway feeds where available fault current runs high. The ETU850 release supports communication (the listing flags a communication function present), so you can pull trip data and status into a BMS or SCADA layer without adding a separate metering module. Lifecycle status is listed as current — this is an active catalog item from Siemens, not a phase-out or NRND line. That means factory support, firmware updates (if applicable), and replacement parts are available through normal Siemens distribution channels. The adjustable release range (minimum 150 A, maximum 1 200 A) suggests the ETU850 can be set for a wide pickup window, though the frame itself is sized for 100 A continuous.","metaTitle":"Siemens 3VA2110-8KP36-0AA0 SENTRON MCCB, 100 A, 3-Pole, 440","metaDescription":"Siemens 3VA2110-8KP36-0AA0 SENTRON molded case circuit breaker. 100 A continuous, 3-pole, ETU850 release. 440 kA at 240 V. Current lifecycle. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 200 A","Minimum":"150 A","at 240 V":"440 kA","at 415 V":"330 kA","at 440 V":"330 kA","at 500 V":"220 kA","at 690 V":"52.5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"100 A","at 60 °C":"100 A","at 65 °C":"100 A","at 70 °C":"100 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"7.7 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU850","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"L","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=430973&mlfb=3VA2110-8KP36-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2110-8KP36-0AA0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2110-8KP36-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2110-8KP36-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}