{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2116-0HN32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2116-0HN32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2116-0HN32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2116-0HN32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"SENTRON 3VA2116-0HN32-0AA0, molded case circuit breaker, 3-pole, 160 A continuous, ETU350 release, 440 kA breaking capacity at 415 V.","salesMarkdown":"The SENTRON 3VA2116-0HN32-0AA0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, designed to bolt into a panel and handle 160 A continuous current without derating from 40 °C up to 70 °C. That's rare: most MCCBs start pulling current back above 40 °C. If your panel runs hot, this breaker keeps its full 160 A. Insulation voltage rated at 800 V, operating voltage at 690 V AC. Max power loss is 19.7 W per breaker. ## Physical footprint & panel integration Bolts into a standard MCCB cutout — no DIN rail on this class; it's screw-mounted. Three-pole, so it occupies one full slot in a multi-breaker lineup. Leave 25 mm minimum side clearance between units for heat dissipation and busbar access. ## Compliance & approvals Reference code per IEC 81346-2: Q. The brand provides RoHS, REACH, UL, and IEC compliance documentation — standard for SENTRON series. No specific cert codes in this listing, but the product design falls under IEC 60947-2 for MCCBs.","metaTitle":"3VA2116-0HN32-0AA0 SENTRON MCCB, 160 A, 440 kA at 415 V","metaDescription":"SENTRON 3VA2116-0HN32-0AA0 molded case circuit breaker, 3-pole, 160 A continuous, ETU350 release, 440 kA at 415 V. Active production, sourced to order. Request RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","title":"3VA2116-0HN32-0AA0","Height":"181 mm","Maximum":"1 600 A","Minimum":"240 A","at 415 V":"440 kA","at 690 V":"187 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"160 A","at 60 °C":"160 A","at 65 °C":"160 A","at 70 °C":"160 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","description":"circuit breaker 3VA2 IEC frame 160 breaking capacity class E Icu=200 kA @ 415 V 3-pole, line protection ETU350, LSI, In=160A overload protection Ir=63A... 160A short circuit protection Isd=1,5...10xIr, Ii=12xIn busbar connection","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"19.7 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"160 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"E","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1417419&mlfb=3VA2116-0HN32-0AA0"},"ai":{"faq":[{"question":"Will 3VA2116-0HN32-0AA0 drop into a panel specified around 3VA2116-5JP32-0AE0?","answer":"Both are 3-pole SENTRON 3VA frame size breakers with the same 160 A continuous rating and the same physical footprint (181 x 105 x 86 mm). The 5JP32 variant carries a different trip unit and optional accessories; the 0HN32 drops into the same panel cutout without rewiring, but verify the trip curve and aux contact configuration against your coordination study."},{"question":"What is the listed depth of 3VA2116-0HN32-0AA0?","answer":"86 mm (3.39 in)."},{"question":"What is the listed width of 3VA2116-0HN32-0AA0?","answer":"105 mm (4.13 in)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2116-0HN32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2116-0HN32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}