{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2116-0KP32-0AH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2116-0KP32-0AH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2116-0KP32-0AH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2116-0KP32-0AH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 series, molded case circuit breaker, IEC frame 160, 3-pole, breaking capacity class E, Icu=200 kA at 415 V, line protection ETU850, LSI, In=160 A, Ir=63...160 A, Isd=0.6...10xIn, Ii=1.5...12xIn, busbar connection, 2 auxiliary switch changeover + 1 trip alarm switch changeover.","salesMarkdown":"The Siemens 3VA2116-0KP32-0AH0 is a SENTRON 3VA2 molded case circuit breaker on an IEC frame 160, rated for a maximum of 256 A and a minimum of 32 A. The ETU850 electronic trip unit with LSI protection (long-time, short-time, instantaneous) gives you adjustable overload pickup Ir from 63 A to 160 A, short-time pickup Isd from 0.6 to 10xIn, and instantaneous pickup Ii from 1.5 to 12xIn. That adjustability lets you coordinate selectivity downstream without swapping trip units — set Ir to match the cable ampacity, then dial Isd to ride through motor inrush. Busbar connection on both sides — no lug kit to source separately if your panel uses a busbar distribution system.","metaTitle":"Siemens 3VA2116-0KP32-0AH0 Circuit Breaker, 256 A, IEC Frame","metaDescription":"Siemens 3VA2116-0KP32-0AH0 SENTRON 3VA2 molded case circuit breaker, 256 A max, 32 A min, IEC frame 160, 200 kA Icu at 415 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"title":"3VA2116-0KP32-0AH0","Maximum":"256 A","Minimum":"32 A","description":"circuit breaker 3VA2 IEC frame 160 breaking capacity class E Icu=200 kA @ 415 V 3-pole, line protection ETU850, LSI, In=160A overload protection Ir=63A... 160A short circuit protection Isd=0,6...10xIn, Ii=1,5...12xIn busbar connection circuit breaker 3VA2 IEC frame 160 breaking capacity class E Icu=200 kA @ 415 V 3-pole, line protection ETU850, LSI, In=160A overload protection Ir=63A... 160A short circuit 2 AUXILIARY SWITCH CHANGEOVER H 1 TRIP ALARM SWITCH CHANGEOVER","lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1511060&mlfb=3VA2116-0KP32-0AH0"},"ai":{"faq":[{"question":"What is 3VA2116-0KP32-0AH0's listed maximum and minimum current?","answer":"The listed maximum is 256 A and the minimum is 32 A, covering the adjustable trip range of the ETU850 unit."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2116-0KP32-0AH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2116-0KP32-0AH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}