{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2116-5HL32-0HA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2116-5HL32-0HA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2116-5HL32-0HA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2116-5HL32-0HA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2116-5HL32-0HA0, molded case circuit breaker, 3-pole, 160 A rated continuous current, 187 kA interrupting at 240 V, ETU320 electronic trip unit, shunt trip release, line protection version.","salesMarkdown":"Interrupting capacity hits 187 kA at 240 V, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 4.25 kA at 690 V — so the SCCR headroom is substantial on lower-voltage secondary taps, but drops off sharply above 500 V. If you need those, you're looking at a different suffix. Derating starts at 55 °C (154 A), then 148 A at 60 °C, 142 A at 65 °C, and 136 A at 70 °C. Maximum power loss is 25.5 W. That's modest for a 160 A frame, but in a sealed, high-density panel, add it to your thermal budget. If you're replacing just the trip unit or the switch body, those are the sub-components to cross-reference.","metaTitle":"Siemens 3VA2116-5HL32-0HA0 SENTRON MCCB, 160 A, 3-Pole, 187","metaDescription":"Siemens SENTRON 3VA2116-5HL32-0HA0 molded case circuit breaker, 160 A rated continuous current, 3-pole, 187 kA interrupting at 240 V. Current-production part, quoted to order. Sour","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"79 kA","at 690 V":"4.25 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"154 A","at 60 °C":"148 A","at 65 °C":"142 A","at 70 °C":"136 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"25.5 W","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"160 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2116-5HL32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL30","Design of the overcurrent release":"ETU320","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"160 A","Adjustable response value current / li max.":"1 600 A","Adjustable response value current / li min.":"240 A","Adjustable response value current / lr min.":"63 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LI","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=234776&mlfb=3VA2116-5HL32-0HA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2116-5HL32-0HA0/alternatives.json"},"ai":{"faq":[{"question":"Does 3VA2116-5HL32-0HA0 include a shunt trip?","answer":"Yes, it has a built-in shunt trip release (STL) as the auxiliary release. No undervoltage release, no auxiliary contacts, no communication module."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2116-5HL32-0HA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2116-5HL32-0HA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}