{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2116-5HL32-0KL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2116-5HL32-0KL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2116-5HL32-0KL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2116-5HL32-0KL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2116-5HL32-0KL0, molded case circuit breaker, 3-pole, 160 A, line protection, ETU320 release, 187 kA at 240 V.","salesMarkdown":"The Siemens SENTRON 3VA2116-5HL32-0KL0 is a 3-pole molded case circuit breaker rated for 160 A continuous current at 40 °C, with an ETU320 electronic trip unit providing adjustable overload and short-circuit protection. The breaker carries 160 A all the way to 50 °C; above that, derate to 154 A at 55 °C and 136 A at 70 °C — a curve to check if your enclosure runs hot. This is a line-protection variant (no ground-fault module, no communication, no undervoltage release), built for straightforward feeder or main-breaker duty in a distribution panel. A shunt trip (STL) is integrated for remote tripping — useful for emergency-stop or fire-safety interlocks. The 3VA2116 frame measures 105 mm wide × 181 mm tall × 86 mm deep — a standard SENTRON 3VA2 footprint that drops into the same mounting cutout as other 160 A MCCBs in the family. If your panel was laid out for the 3VA2116-5HL32-0AK0 (the same breaker without the shunt trip), the 3VA2116-5HL32-0KL0 shares the identical mechanical envelope and bus-bar connection pattern; the only difference is the integrated STL coil, which adds a pair of control wires. No rewiring of the main power path is needed.","metaTitle":"Siemens 3VA2116-5HL32-0KL0 SENTRON MCCB, 160 A, 187 kA at 24","metaDescription":"Siemens SENTRON 3VA2116-5HL32-0KL0 molded case circuit breaker, 160 A rated continuous current, 187 kA breaking capacity at 240 V. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"79 kA","at 690 V":"4.25 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"154 A","at 60 °C":"148 A","at 65 °C":"142 A","at 70 °C":"136 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"25.5 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"160 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2116-5HL32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL33","Design of the overcurrent release":"ETU320","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"160 A","Adjustable response value current / li max.":"1 600 A","Adjustable response value current / li min.":"240 A","Adjustable response value current / lr min.":"63 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"4","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=141330&mlfb=3VA2116-5HL32-0KL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2116-5HL32-0KL0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this MCCB at different voltages?","answer":"187 kA at 240 V, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 4.25 kA at 690 V."},{"question":"Will 3VA2116-5HL32-0KL0 fit in a panel designed for 3VA2116-5HL32-0AK0?","answer":"Yes — the mechanical dimensions (105 mm wide × 181 mm tall × 86 mm deep) and bus-bar pattern are identical. The only difference is the integrated shunt trip on the -0KL0, which adds two control wires for the STL coil."},{"question":"What auxiliary contacts come with this breaker?","answer":"It ships with 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch (HQ type) — all factory-integrated."},{"question":"How do I get current pricing and availability for 3VA2116-5HL32-0KL0?","answer":"Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2116-5HL32-0KL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2116-5HL32-0KL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}