{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2116-5HL36-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2116-5HL36-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2116-5HL36-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2116-5HL36-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2116-5HL36-0AA0, molded case circuit breaker, 3-pole, 160 A rated continuous current, ETU320 electronic trip unit, line protection design, breaking capacities up to 187 kA at 240 V.","salesMarkdown":"The trip unit gives you adjustable overload and short-circuit settings, so you can dial in coordination without swapping hardware. Breaking capacity is what you really care about when a fault hits. At 240 V it's rated 187 kA, at 415 V and 440 V it holds 121 kA, at 500 V it drops to 75.6 kA, and at 690 V it's 3.7 kA. The 690 V number is low enough that you'd want to verify coordination if you're running a 690 V line. It's a standard SENTRON 3VA form factor — bolts into a panel on a mounting plate or onto a DIN rail adapter if you use the optional rail foot. The 105 mm width per pole is typical for this class; three poles take up about 4.13 inches of rail space. No trip indicator on the front, so you'll need a separate status contact if you want remote blown-fuse indication.","metaTitle":"Siemens 3VA2116-5HL36-0AA0 SENTRON MCCB, 160 A, 3-Pole, ETU3","metaDescription":"Siemens SENTRON 3VA2116-5HL36-0AA0 molded case circuit breaker, 160 A continuous, 3-pole, ETU320 trip unit. Breaking capacity up to 187 kA at 240 V. Active production. Quoted to or","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 600 A","Minimum":"240 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3.7 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"160 A","at 60 °C":"160 A","at 65 °C":"160 A","at 70 °C":"160 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"160 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$341.63","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=432777&mlfb=3VA2116-5HL36-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2116-5HL36-0AA0/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for 3VA2116-5HL36-0AA0?","answer":"Rated continuous current is 160 A, insulation voltage is 800 V, and breaking capacity ranges from 187 kA at 240 V down to 3.7 kA at 690 V. The ETU320 electronic trip unit provides adjustable protection settings."},{"question":"Where can I buy 3VA2116-5HL36-0AA0?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2116-5HL36-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2116-5HL36-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}