{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2116-5HL46-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2116-5HL46-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2116-5HL46-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2116-5HL46-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2116-5HL46-0AA0, molded case circuit breaker, 4-pole, 160 A continuous, ETU320 electronic trip unit, 187 kA at 240 V, 86 mm depth, 140 mm width, 181 mm height.","salesMarkdown":"The Siemens SENTRON 3VA2116-5HL46-0AA0 is a 4-pole molded case circuit breaker (MCCB) rated for 160 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. It carries an ETU320 electronic trip unit, which means the protection curve is adjustable for selective coordination downstream. The interrupting ratings climb to 187 kA at 240 V AC, drop to 121 kA at 415 V and 440 V, then to 75.6 kA at 500 V, and settle at 3.7 kA at 690 V. No undervoltage release or shunt trip is built in.","metaTitle":"Siemens 3VA2116-5HL46-0AA0 SENTRON MCCB, 160 A, 4-Pole, 187","metaDescription":"Siemens SENTRON 3VA2116-5HL46-0AA0 molded case circuit breaker, 160 A continuous, 4-pole, ETU320 release, 187 kA at 240 V. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"140 mm","Height":"181 mm","Maximum":"1 600 A","Minimum":"240 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3.7 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"160 A","at 60 °C":"160 A","at 65 °C":"160 A","at 70 °C":"160 A","Depth [In]":"3.39 in","Width [In]":"5.51 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"4","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"160 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 50%; 100%","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=255195&mlfb=3VA2116-5HL46-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2116-5HL46-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Will 3VA2116-5HL46-0AA0 drop into a panel that was specified around 3VA2116-5JP32-0AE0 without rewiring?","answer":"Both are 4-pole SENTRON 3VA breakers with the same physical footprint (86 mm deep, 140 mm wide, 181 mm high), so mechanical fit is identical. The electrical difference is the trip unit: the -5HL46-0AA0 carries an ETU320 electronic release, while the -5JP32-0AE0 uses a different trip curve. Verify the protection settings match your coordination study before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2116-5HL46-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2116-5HL46-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}