{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2116-5HN32-0BB0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2116-5HN32-0BB0","canonicalUrl":"https://aoctrl.com/siemens/3VA2116-5HN32-0BB0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2116-5HN32-0BB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA series, molded case circuit breaker, 3VA2116-5HN32-0BB0, 3-pole, 160 A, ETU350 electronic trip unit, line protection.","salesMarkdown":"Its breaking capacity reaches 187 kA at 240 V, 121 kA at 415 V and 440 V, 76 kA at 500 V, and 3.8 kA at 690 V — so at standard 400 V distribution it clears faults up to 121 kA without cascading upstream. That SCCR headroom matters when you're coordinating a panel for a shutdown window: you want the main breaker to hold, not blow a hole in your selectivity study. ## Trip unit and thermal performance The ETU350 electronic trip unit offers adjustable long-time delay (tr) from 0.5 to 17 seconds and short-time delay (tsd) from 0.02 to 0.4 seconds, giving you flexibility for coordination with downstream breakers. Maximum power loss is 25.5 W, so ventilation planning is straightforward.","metaTitle":"Siemens 3VA2116-5HN32-0BB0 SENTRON MCCB, 160 A, 3-Pole, ETU3","metaDescription":"Siemens SENTRON 3VA2116-5HN32-0BB0 molded case circuit breaker, 160 A, 3-pole, ETU350 release. Breaking capacity 187 kA at 240 V. Current lifecycle stage. Quoted to order against R","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"76 kA","at 690 V":"3.8 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"160 A","at 60 °C":"160 A","at 65 °C":"160 A","at 70 °C":"160 A","Width [in]":"4.1 in","Height [in]":"7.1 in","Number of poles":"3","Product version":"Line protection","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"25.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"160 A","Rated insulation voltage Ui":"800 V","Ground fault monitoring version":"Without","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.4 s","Adjustable response value time / tsd min.":"0.02 s","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"160 A","Adjustable response value current / li max.":"1 600 A","Adjustable response value current / li min.":"1 600 A","Adjustable response value current / lr min.":"63 A","Adjustable response value current / Isd max.":"1 600 A","Adjustable response value current / Isd min.":"240 A","Neutral conductors / upgradeable/retrofittable":"No","Protective function of the overcurrent release":"LSI","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=799137&mlfb=3VA2116-5HN32-0BB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2116-5HN32-0BB0/alternatives.json"},"ai":{"faq":[{"question":"Who supplies 3VA2116-5HN32-0BB0 and how is it quoted for volume purchases?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time."},{"question":"What is 3VA2116-5HN32-0BB0's listed depth?","answer":"The listed depth is 86 mm."},{"question":"What is 3VA2116-5HN32-0BB0's listed width?","answer":"The listed width is 105 mm."},{"question":"What compliance documentation does this brand provide for 3VA2116-5HN32-0BB0?","answer":"As a Siemens SENTRON MCCB, it carries the standard CE, UL, and IEC certifications for molded case circuit breakers. Specific RoHS and REACH declarations are available through the manufacturer's documentation portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2116-5HN32-0BB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2116-5HN32-0BB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}