{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2116-5HN32-0CH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2116-5HN32-0CH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2116-5HN32-0CH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2116-5HN32-0CH0","rawCanonicalId":null},"summary":{"shortDescription":"SENTRON 3VA2116-5HN32-0CH0, molded case circuit breaker, 3-pole, 160 A continuous, breaking capacity 187 kA at 240 V AC, 121 kA at 415 V AC, undervoltage release, 2 aux switches + 1 trip alarm.","salesMarkdown":"The SENTRON 3VA2116-5HN32-0CH0 is a 3-pole molded case circuit breaker (MCCB) rated for 160 A continuous current, with a breaking capacity of 187 kA at 240 V AC and 121 kA at 415 V AC — that means it can safely interrupt fault currents up to those levels without welding its contacts or cascading the fault upstream. The UVR ensures the breaker drops out if control voltage falls below a set threshold — a standard requirement for safety circuits that need to isolate on loss of control power. The undervoltage release requires a separate control voltage feed — verify polarity and voltage rating against the coil nameplate before energizing.","metaTitle":"SENTRON 3VA2116-5HN32-0CH0 MCCB, 160 A, 3-Pole, 187 kA at 24","metaDescription":"SENTRON 3VA2116-5HN32-0CH0 molded case circuit breaker, 160 A continuous, 3-pole, breaking capacity 187 kA at 240 V AC. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 600 A","Minimum":"1 600 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3.7 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"160 A","at 60 °C":"160 A","at 65 °C":"160 A","at 70 °C":"160 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"28 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21165HN320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"160 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB24","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=470735&mlfb=3VA2116-5HN32-0CH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2116-5HN32-0CH0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this MCCB at 415 V?","answer":"121 kA at 415 V AC, which is the same rating as at 440 V. At 690 V it drops to 3.7 kA, so verify the available fault current at your service voltage."},{"question":"Where can I buy 3VA2116-5HN32-0CH0?","answer":"Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time."},{"question":"Does this breaker include an undervoltage release?","answer":"Yes, it is equipped with an undervoltage release (UVR) as the auxiliary release, plus two auxiliary switches and one trip alarm switch."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2116-5HN32-0CH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2116-5HN32-0CH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}