{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2116-5HN36-0BA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2116-5HN36-0BA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2116-5HN36-0BA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2116-5HN36-0BA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2116-5HN36-0BA0, molded case circuit breaker, 3-pole, 160 A, line protection, ETU350 release, 187 kA at 240 V, 121 kA at 415 V, undervoltage release.","salesMarkdown":"The Siemens SENTRON 3VA2116-5HN36-0BA0 is a 3-pole molded case circuit breaker (MCCB) rated 160 A continuous at 40 °C, with an ETU350 electronic trip unit for line protection. The interrupting ratings are the headline: 187 kA at 240 V, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 4.25 kA at 690 V. The 160 A rating holds flat to 50 °C; above that it derates to 154 A at 55 °C, 148 A at 60 °C, 142 A at 65 °C, and 136 A at 70 °C (–). No auxiliary contact block is fitted; if you need signaling, add the separate auxiliary contact kit. The ETU350 is the overcurrent release — it's electronic, so it offers adjustable trip curves (long-time, short-time, instantaneous, ground fault) via the front dials. No communication function or phase failure detection on this variant. Power loss is 28 W max — factor that into enclosure thermal rise.","metaTitle":"Siemens 3VA2116-5HN36-0BA0 SENTRON MCCB, 160 A, 187 kA","metaDescription":"Siemens SENTRON 3VA2116-5HN36-0BA0 molded case circuit breaker, 160 A rated, 187 kA at 240 V, ETU350 release, undervoltage release. Current production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"79 kA","at 690 V":"4.25 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"154 A","at 60 °C":"148 A","at 65 °C":"142 A","at 70 °C":"136 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"28 W","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"160 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2116-5HN36-0AA0","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB11","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.4 s","Adjustable response value time / tsd min.":"0.02 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"160 A","Adjustable response value current / li max.":"1 600 A","Adjustable response value current / li min.":"1 600 A","Adjustable response value current / lr min.":"63 A","Adjustable response value current / Isd max.":"1 600 A","Adjustable response value current / Isd min.":"240 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LSI","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (6-120 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=54498&mlfb=3VA2116-5HN36-0BA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2116-5HN36-0BA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2116-5HN36-0BA0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the interrupting rating of this MCCB?","answer":"187 kA at 240 V, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 4.25 kA at 690 V (–)."},{"question":"What trip unit does this breaker use?","answer":"It uses the ETU350 electronic overcurrent release, offering adjustable long-time, short-time, instantaneous, and ground-fault protection."},{"question":"Does this breaker include an undervoltage release?","answer":"Yes, it is factory-fitted with an undervoltage release (UVR)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2116-5HN36-0BA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2116-5HN36-0BA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}