{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2116-5HN36-0JA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2116-5HN36-0JA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2116-5HN36-0JA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2116-5HN36-0JA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2116-5HN36-0JA0, molded case circuit breaker, 3-pole, 160 A, 187 kA at 240 V, ETU350 trip unit, shunt trip.","salesMarkdown":"The overcurrent release is an ETU350 electronic trip unit, adjustable for coordination studies. Breaking capacity hits 187 kA at 240 V, 121 kA at 415 V, and 79 kA at 500 V; at 690 V it drops to 4.25 kA, so watch your system voltage when sizing for fault current. The breaker holds 160 A straight through 50 °C ambient; above that it derates to 154 A at 55 °C, 148 A at 60 °C, 142 A at 65 °C, and 136 A at 70 °C.","metaTitle":"Siemens 3VA2116-5HN36-0JA0 SENTRON MCCB, 160 A, 187 kA at 24","metaDescription":"Siemens SENTRON 3VA2116-5HN36-0JA0 molded case circuit breaker, 160 A rated, 187 kA breaking at 240 V. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"79 kA","at 690 V":"4.25 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"154 A","at 60 °C":"148 A","at 65 °C":"142 A","at 70 °C":"136 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"25.5 W","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"160 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2116-5HN36-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.4 s","Adjustable response value time / tsd min.":"0.02 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"160 A","Adjustable response value current / li max.":"1 600 A","Adjustable response value current / li min.":"1 600 A","Adjustable response value current / lr min.":"63 A","Adjustable response value current / Isd max.":"1 600 A","Adjustable response value current / Isd min.":"240 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LSI","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (6-120 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=80348&mlfb=3VA2116-5HN36-0JA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2116-5HN36-0JA0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2116-5HN36-0JA0 at 415 V?","answer":"At 415 V the breaker is rated for 121 kA breaking capacity. At 240 V it reaches 187 kA; at 500 V it drops to 79 kA; at 690 V it is 4.25 kA."},{"question":"What trip unit does 3VA2116-5HN36-0JA0 use?","answer":"It uses an ETU350 electronic overcurrent release. The breaker also includes a shunt trip (STL) auxiliary release but no undervoltage release, no auxiliary contacts, and no communication function."},{"question":"Where can I buy 3VA2116-5HN36-0JA0?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2116-5HN36-0JA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2116-5HN36-0JA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}