{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2116-5HN42-0HC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2116-5HN42-0HC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2116-5HN42-0HC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2116-5HN42-0HC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2116-5HN42-0HC0, molded case circuit breaker, 1600 A, 4-pole, 187 kA at 240 V, line protection design.","salesMarkdown":"It carries 187 kA interrupting capacity at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V — the SCCR curve drops sharply above 500 V, so verify coordination at the system voltage. Maximum power loss is 25.5 W. Dimensions are 181 mm height, 140 mm width, 86 mm depth. ## Integration & Panel Fit Mounts in a standard switchgear enclosure or MCC bucket. The 140 mm width and 86 mm depth fit common distribution panel cutouts. Auxiliary contacts and shunt trip come pre-installed — no field-addon kit needed for the basic release functions. No communication module on board; this is a standalone line-protection breaker, not a power-monitoring device.","metaTitle":"Siemens 3VA2116-5HN42-0HC0 SENTRON MCCB, 1600 A, 187 kA at 2","metaDescription":"Siemens 3VA2116-5HN42-0HC0 SENTRON molded case circuit breaker, 1600 A rated, 187 kA interrupting at 240 V. 4-pole, line protection. Active production. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"140 mm","Height":"181 mm","Maximum":"1 600 A","Minimum":"1 600 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3.7 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"160 A","at 60 °C":"160 A","at 65 °C":"160 A","at 70 °C":"160 A","Depth [In]":"3.39 in","Width [In]":"5.51 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"4","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA21165HN420AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"160 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 50%; 100%","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL30","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=630501&mlfb=3VA2116-5HN42-0HC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2116-5HN42-0HC0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting capacity of 3VA2116-5HN42-0HC0 at 415 V?","answer":"121 kA at 415 V, which is the same rating as at 440 V. At 500 V it drops to 75.6 kA, and at 690 V to 3.7 kA."},{"question":"Does this MCCB include a shunt trip or undervoltage release?","answer":"It includes a shunt trip (STL) auxiliary release and two HQ auxiliary switches, but no undervoltage release and no ground-fault monitoring."},{"question":"Where can I buy 3VA2116-5HN42-0HC0 and how is it quoted?","answer":"Sourced to order through independent distribution. Submit an RFQ for current availability and pricing — no stock or price figures are published on this listing."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2116-5HN42-0HC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2116-5HN42-0HC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}