{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2116-5KP32-0BH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2116-5KP32-0BH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2116-5KP32-0BH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2116-5KP32-0BH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2116-5KP32-0BH0, molded case circuit breaker, 3-pole, 160 A (at 40 °C), ETU850 electronic trip unit, breaking capacity 187 kA at 240 V, 121 kA at 415 V, 79 kA at 500 V, 4.25 kA at 690 V.","salesMarkdown":"The 3VA2116-5KP32-0BH0: The ETU850 is a communicating trip unit — the breaker carries a communication function, so you can pull event logs and settings over the bus. An undervoltage release (UVR) is integrated, and the basic switch variant is 3VA2116-5KP32-0AA0. At 55 °C it derates to 154 A, at 60 °C to 148 A, at 65 °C to 142 A, and at 70 °C to 136 A.","metaTitle":"Siemens 3VA2116-5KP32-0BH0 SENTRON MCCB, 160A, 3-Pole, ETU85","metaDescription":"Siemens 3VA2116-5KP32-0BH0 SENTRON molded case circuit breaker, 160A rated at 40°C, 3-pole, ETU850 electronic trip unit, 187 kA at 240 V. Active production. Sourced to order agains","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"79 kA","at 690 V":"4.25 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"154 A","at 60 °C":"148 A","at 65 °C":"142 A","at 70 °C":"136 A","Trip Indicator":"Yes","Number Of Poles":"3","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Communication Function":"Yes","Phase Failure Detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"28 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Of The Supplied Basic Switch":"3VA2116-5KP32-0AA0","Design Of The Auxiliary Release":"Undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Tension assignée d'isolement Ui":"800 V","Design Of The Overcurrent Release":"ETU850","protection class IP / on the front":"IP40","reference code / acc. to IEC 81346-2":"Q","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB11","Undervoltage Release With Leading Contact":"No","Product Extension / Optional / Motor Drive":"Yes","Adjustable response value current / lg min.":"0.5 s","Adjustable response value current / li max.":"1 600 A","Adjustable response value current / li min.":"240 A","Neutral conductors / upgradeable/retrofittable":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Switching Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"Lug terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=483807&mlfb=3VA2116-5KP32-0BH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2116-5KP32-0BH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2116-5KP32-0BH0 and what is the lead time?","answer":"Sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no fixed lead time published here, but we quote firm dates with each RFQ."},{"question":"Will 3VA2116-5KP32-0BH0 drop into a panel specified around 3VA2116-5JP32-0AE0 without rewiring?","answer":"Yes — both share the same 105 mm width and 3-pole SENTRON 3VA2 frame, so the physical footprint, busbar centers, and DIN-rail clip are identical. The difference is the trip unit: the -5KP32-0BH0 carries the ETU850 electronic unit, while the -5JP32-0AE0 uses a different trip curve. No rewiring required, but verify the protection settings match your coordination study."},{"question":"What is the breaking capacity of this MCCB at different voltages?","answer":"187 kA at 240 V, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 4.25 kA at 690 V. The steep drop at 690 V is typical for this frame size — if your system runs 690 V, check that 4.25 kA exceeds your prospective fault current."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2116-5KP32-0BH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2116-5KP32-0BH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}