{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2116-5KP32-0DA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2116-5KP32-0DA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2116-5KP32-0DA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2116-5KP32-0DA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 series, molded case circuit breaker (MCCB), 3VA2116-5KP32-0DA0, 3-pole, 160 A continuous, 187 kA breaking at 240 V, line protection with undervoltage release.","salesMarkdown":"The Siemens 3VA2116-5KP32-0DA0 is a SENTRON 3VA2 molded case circuit breaker (MCCB) rated for 160 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. Its 3-pole design carries a breaking capacity of 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V. Mounts on a DIN rail or panel plate; dimensions are 105 mm wide, 181 mm high, 86 mm deep — that's 4.13 by 7.13 by 3.39 inches. The 3-pole footprint matches standard SENTRON 3VA2 cutouts. No ground-fault monitoring module is included. Designed for line protection — that means it's the main feeder breaker or large subfeed in a distribution panel, not a motor-circuit protector. The 160 A continuous rating with flat derating to 70 °C makes it a solid choice for high-ambient enclosures or outdoor cabinets where other breakers would need to be oversized.","metaTitle":"Siemens 3VA2116-5KP32-0DA0 SENTRON MCCB, 160 A, 3-Pole","metaDescription":"Siemens 3VA2116-5KP32-0DA0 SENTRON molded case circuit breaker, 160 A continuous, 3-pole, 187 kA at 240 V. Current lifecycle, available to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 600 A","Minimum":"240 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3.7 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"160 A","at 60 °C":"160 A","at 65 °C":"160 A","at 70 °C":"160 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"28 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Of The Supplied Basic Switch":"3VA21165KP320AA0","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"160 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU850","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=396959&mlfb=3VA2116-5KP32-0DA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2116-5KP32-0DA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2116-5KP32-0DA0 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What are the key ratings for 3VA2116-5KP32-0DA0?","answer":"160 A continuous current, 3-pole, 187 kA breaking capacity at 240 V, 800 V rated insulation voltage, and 28 W max power loss."},{"question":"What is the depth of 3VA2116-5KP32-0DA0?","answer":"86 mm (3.39 inches)."},{"question":"What is the width of 3VA2116-5KP32-0DA0?","answer":"105 mm (4.13 inches)."},{"question":"Does 3VA2116-5KP32-0DA0 include an undervoltage release?","answer":"Yes, it has a built-in undervoltage release (UVR)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2116-5KP32-0DA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2116-5KP32-0DA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}