{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2116-5KP32-0DC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2116-5KP32-0DC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2116-5KP32-0DC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2116-5KP32-0DC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 molded case circuit breaker, 3VA2116-5KP32-0DC0, 160 A, 3-pole, line protection with undervoltage release and communication function.","salesMarkdown":"## SENTRON 3VA2 MCCB — 160 A, 3-Pole, Line Protection Breaking capacity is rated 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3.7 kA at 690 V — so at typical 400 V distribution voltages it clears fault currents well above most panel SCCR requirements without cascading upstream. The breaker ships with two HQ auxiliary switches and the undervoltage release pre-installed; the basic switch model is 3VA21165KP320AA0. No ground-fault monitoring module is included on this variant. ## Panel Fit and Thermal Performance Dimensions are 105 mm wide, 181 mm tall, and 86 mm deep — the width is standard for a 3-pole SENTRON 3VA2 frame, so it drops into existing 3VA2 panel cutouts without modification. Maximum power loss is 28 W, manageable with natural convection in most enclosures. The unit is designed for fixed installation in distribution boards — no DIN-rail mounting on this frame size.","metaTitle":"Siemens 3VA2116-5KP32-0DC0 SENTRON MCCB, 160 A, 3-Pole","metaDescription":"Siemens 3VA2116-5KP32-0DC0 SENTRON molded case circuit breaker, 160 A continuous, 3-pole, 187 kA at 240 V. Active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"1 600 A","Minimum":"240 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"3.7 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"160 A","at 60 °C":"160 A","at 65 °C":"160 A","at 70 °C":"160 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"28 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Of The Supplied Basic Switch":"3VA21165KP320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"160 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU850","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"160 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=354444&mlfb=3VA2116-5KP32-0DC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2116-5KP32-0DC0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2116-5KP32-0DC0 at 415 V?","answer":"121 kA at 415 V. At 240 V it is 187 kA, at 440 V also 121 kA, at 500 V it drops to 75.6 kA, and at 690 V to 3.7 kA."},{"question":"Will 3VA2116-5KP32-0DC0 drop into a panel specified for 3VA2116-5JP32-0AE0?","answer":"Both are 3-pole SENTRON 3VA2 frame breakers sharing the same 105 mm width and mounting footprint, so it should fit the same panel cutout without rewiring. Verify the auxiliary switch configuration and release type on the existing panel drawing before ordering."},{"question":"Where can I buy 3VA2116-5KP32-0DC0 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2116-5KP32-0DC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2116-5KP32-0DC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}