{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2116-6HN32-0AC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2116-6HN32-0AC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2116-6HN32-0AC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2116-6HN32-0AC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2116-6HN32-0AC0, molded case circuit breaker, 3-pole, 160 A, ETU350 electronic trip, 242 kA at 240 V, 187 kA at 415 V, IP40 front.","salesMarkdown":"## Line protection MCCB with ETU350 — 160 A, 242 kA SCCR The Siemens 3VA2116-6HN32-0AC0 is a 3-pole SENTRON molded case circuit breaker rated for line protection, carrying a continuous current Iu of 160 A and an interrupting capacity of 242 kA at 240 V, 187 kA at 415 V, and 121 kA at 500 V. At 55 °C it drops to 154 A, at 60 °C to 148 A, at 65 °C to 142 A, and at 70 °C to 136 A. For a panel that runs warm — say a packed enclosure with drives — the 55 °C derate is the one to budget against. The auxiliary contact version fitted is 2 auxiliary switches HQ, and the breaker includes a latching endurance of 20 000 cycles.","metaTitle":"Siemens 3VA2116-6HN32-0AC0 SENTRON MCCB, 160 A, 242 kA at 24","metaDescription":"Siemens 3VA2116-6HN32-0AC0 SENTRON molded case circuit breaker, 160 A rated continuous, 242 kA interrupting at 240 V. ETU350 release. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"5 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"154 A","at 60 °C":"148 A","at 65 °C":"142 A","at 70 °C":"136 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"25.5 W","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"160 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2116-6HN32-0AA0","Design of the auxiliary release":"Without auxiliary release","Ground fault monitoring version":"Without","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.4 s","Adjustable response value time / tsd min.":"0.02 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"160 A","Adjustable response value current / li max.":"1 600 A","Adjustable response value current / li min.":"1 600 A","Adjustable response value current / lr min.":"63 A","Adjustable response value current / Isd max.":"1 600 A","Adjustable response value current / Isd min.":"240 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=182165&mlfb=3VA2116-6HN32-0AC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2116-6HN32-0AC0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA2116-6HN32-0AC0?","answer":"Submit an RFQ through the storefront; the part is sourced and quoted to order, with availability and pricing confirmed at quote time."},{"question":"What is 3VA2116-6HN32-0AC0's interrupting capacity at 415 V?","answer":"187 kA at 415 V, same as at 440 V. At 500 V it's 121 kA, and at 690 V it drops to 5 kA."},{"question":"What trip unit does 3VA2116-6HN32-0AC0 use?","answer":"The ETU350 electronic trip unit, with adjustable long-time, short-time, instantaneous, and ground-fault protection curves."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2116-6HN32-0AC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2116-6HN32-0AC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}