{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2116-6HN32-0DH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2116-6HN32-0DH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2116-6HN32-0DH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2116-6HN32-0DH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2116-6HN32-0DH0, molded case circuit breaker, 3-pole, 160 A, ETU350 electronic trip unit, line protection, breaking capacity 242 kA at 240 V.","salesMarkdown":"The Siemens SENTRON 3VA2116-6HN32-0DH0 is a 3-pole molded case circuit breaker (MCCB) rated for a continuous current of 160 A, with an ETU350 electronic trip unit for line protection. It handles fault currents up to 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 5 kA at 690 V — so it can sit upstream of a transformer or a large motor feeder and still coordinate with downstream devices without cascading failure. The 160 A rating holds flat from 40 °C up to 50 °C, which covers most panel ambient conditions. Above that, it derates: 154 A at 55 °C, 148 A at 60 °C, 142 A at 65 °C, and 136 A at 70 °C. If your panel runs hot — say next to a drive cabinet or in a poorly ventilated enclosure — that 136 A at 70 °C is the number to size against, not the catalog 160 A. Footprint is 105 mm wide × 181 mm high × 86 mm deep.","metaTitle":"Siemens SENTRON 3VA2116-6HN32-0DH0 MCCB, 160 A, 3-Pole, ETU3","metaDescription":"Siemens SENTRON 3VA2116-6HN32-0DH0 molded case circuit breaker, 160 A, 3-pole, ETU350 release, breaking capacity up to 242 kA at 240 V. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"5 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"154 A","at 60 °C":"148 A","at 65 °C":"142 A","at 70 °C":"136 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"28 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"160 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2116-6HN32-0AA0","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB25","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.4 s","Adjustable response value time / tsd min.":"0.02 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"160 A","Adjustable response value current / li max.":"1 600 A","Adjustable response value current / li min.":"1 600 A","Adjustable response value current / lr min.":"63 A","Adjustable response value current / Isd max.":"1 600 A","Adjustable response value current / Isd min.":"240 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=332911&mlfb=3VA2116-6HN32-0DH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2116-6HN32-0DH0/alternatives.json"},"ai":{"faq":[{"question":"What is 3VA2116-6HN32-0DH0's listed depth (86 mm) on this component line?","answer":"The depth is 86 mm. Width is 105 mm, height is 181 mm."},{"question":"Will 3VA2116-6HN32-0DH0 drop into a panel that was specified around 3VA2116-5HL32-0AK0 without rewiring?","answer":"The 3VA2 frame (this part) is physically larger than the 3VA1 frame that the 5HL variant uses. The 105 mm width and 181 mm height are bigger than the 3VA1 footprint, so you would need to check backplate cutouts and bus-bar spacing before assuming a drop-in fit. The terminal layout and pole spacing are the same SENTRON pattern, but the mounting hole pattern differs between frame sizes."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2116-6HN32-0DH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2116-6HN32-0DH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}