{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2116-6HN32-0JH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2116-6HN32-0JH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2116-6HN32-0JH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2116-6HN32-0JH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2116-6HN32-0JH0, molded case circuit breaker, 3-pole, line protection, rated 160 A at 40 °C, ETU350 electronic release, 242 kA at 240 V, 187 kA at 415 V.","salesMarkdown":"Its interrupting capacity reaches 242 kA at 240 V and 187 kA at both 415 V and 440 V, dropping to 5 kA at 690 V — figures that define its use as a main or feeder breaker in high-fault industrial distribution panels. ## Thermal derating and enclosure planning In a panel with ambient near 55 °C — common in a petrochemical switchroom with no active cooling — expect 154 A available. Maximum power loss is 25.5 W.","metaTitle":"Siemens 3VA2116-6HN32-0JH0 SENTRON MCCB, 160 A, 3-pole, line","metaDescription":"Siemens SENTRON 3VA2116-6HN32-0JH0 molded case circuit breaker, 160 A at 40 °C, 3-pole, ETU350 release, 242 kA at 240 V. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"5 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"154 A","at 60 °C":"148 A","at 65 °C":"142 A","at 70 °C":"136 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"25.5 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"160 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2116-6HN32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.4 s","Adjustable response value time / tsd min.":"0.02 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"160 A","Adjustable response value current / li max.":"1 600 A","Adjustable response value current / li min.":"1 600 A","Adjustable response value current / lr min.":"63 A","Adjustable response value current / Isd max.":"1 600 A","Adjustable response value current / Isd min.":"240 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"160 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=399466&mlfb=3VA2116-6HN32-0JH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2116-6HN32-0JH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2116-6HN32-0JH0?","answer":"This MCCB is sourced to order through independent distribution. Submit an RFQ for current pricing and availability."},{"question":"What are the key ratings of this MCCB?","answer":"Rated continuous current 160 A at 40 °C, interrupting capacity 242 kA at 240 V and 187 kA at 415 V, 3-pole, ETU350 electronic trip unit, shunt trip (STL), 2 aux + 1 alarm switch."},{"question":"What is the depth of 3VA2116-6HN32-0JH0?","answer":"The depth is 86 mm, width 105 mm, height 181 mm."},{"question":"Does this breaker include ground fault protection?","answer":"No, this version is without ground fault monitoring. The ETU350 handles overload and short-circuit only."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2116-6HN32-0JH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2116-6HN32-0JH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}