{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2116-7HN36-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2116-7HN36-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2116-7HN36-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2116-7HN36-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA series molded case circuit breaker, 3VA2116-7HN36-0AA0, 3-pole, 160 A, ETU350 electronic trip unit, 330 kA interrupting at 240 V.","salesMarkdown":"The Siemens SENTRON 3VA2116-7HN36-0AA0 is a 3-pole molded case circuit breaker (MCCB) rated for 160 A continuous current at 40–70 °C with no derating across that range — it holds 160 A all the way up to 70 °C ambient, which is unusual and simplifies panel sizing in hot environments. The interrupting ratings are high: 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3.7 kA at 690 V — so it can sit ahead of a high-fault panel without needing a current-limiting fuse upstream. Dimensions are 181 mm high, 105 mm wide, 86 mm deep — a standard 3-pole MCCB footprint for the 3VA frame size. Maximum power loss is 25.5 W, which matters for enclosure thermal rise calculations when multiple breakers are ganged in a panel.","metaTitle":"Siemens 3VA2116-7HN36-0AA0 SENTRON MCCB, 160 A, 3-Pole, ETU3","metaDescription":"Siemens SENTRON 3VA2116-7HN36-0AA0 MCCB, 160 A continuous, 3-pole, ETU350 electronic trip, 330 kA at 240 V. Current production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"3.7 kA","at 40 °C":"160 A","at 45 °C":"160 A","at 50 °C":"160 A","at 55 °C":"160 A","at 60 °C":"160 A","at 65 °C":"160 A","at 70 °C":"160 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Courant permanent assigné Iu":"160 A","Ground-Fault Monitoring Version":"Without","Tension assignée d'isolement Ui":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","reference code / acc. to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Adjustable response value current / li max.":"1 600 A","Adjustable response value current / li min.":"1 600 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"C","Max. rated operational current of the frame size":"160 A","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"double-sided box terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (6-120 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/83eff65c44469ff46b70582785c85926.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=274887&mlfb=3VA2116-7HN36-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2116-7HN36-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Who supplies 3VA2116-7HN36-0AA0 and how is it quoted for volume?","answer":"This MCCB is sourced through independent distribution channels and quoted to order against an RFQ. Volume pricing and lead time are confirmed at quote time — no published list price applies."},{"question":"What are the key ratings of 3VA2116-7HN36-0AA0?","answer":"160 A continuous current (no derating up to 70 °C), 3-pole, ETU350 electronic trip, interrupting capacity of 330 kA at 240 V and 242 kA at 415 V. Rated insulation voltage is 800 V."},{"question":"What is the depth of 3VA2116-7HN36-0AA0?","answer":"The depth is 86 mm (3.39 in). Combined with 105 mm width and 181 mm height, it fits standard 3-pole MCCB panel cutouts for the 3VA frame."},{"question":"Will 3VA2116-7HN36-0AA0 drop into a panel specified for 3VA2110-7HK42-0AA0?","answer":"Both are 3-pole SENTRON 3VA frame breakers with the same 105 mm width and 181 mm height, so the mechanical footprint is identical. The difference is in the trip unit and current rating — verify the downstream protection coordination and busbar ampacity before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2116-7HN36-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2116-7HN36-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}